2. Before installation
2.1 Check that the voltage between neutral and earth does
not exceed 10 volts.
If this voltage does exceed 10 volts, the installation is
unsafe.
Find and rectify the cause of this fault before proceeding.
2.2 Make sure that the supply voltage is suitable for the unit.
Supply Rated
Voltage (VRMS)
Unit Voltage
Range (VRMS)
ESP 120 M1
Phase to Neutral/Earth
110/120/127
90-150
ESP 208 M1 and
ESP 208 M1R Phase to Phase
190/208/220
156-260
ESP 240 M1
Phase to Neutral/Earth
220/230/240
200-280
ESP 415 M1 and
ESP 415 M1R Phase to Phase
380/400/415
346-484
ESP 277 M1
Phase to Neutral/Earth
240/254/277
232-350
ESP 480 M1 and
ESP 480 M1R Phase to Phase
415/440/480
402-600
Installation instructions for mains wire-in protectors | 2/1