PROCEDURE FOR QUALITY CHECKS

 

 

 

OF DR IEC  

 

ENTELLIGUARD G , MPACT &ENTELLIGUARD L FAMILY

 

 

 

 

Содержание ENTELLIGUARD G

Страница 1: ...1SDH00xxxxxxx ECN000xxxxx Rev A PROCEDURE FOR QUALITY CHECKS OF DR IEC ENTELLIGUARD G MPACT ENTELLIGUARD L FAMILY ...

Страница 2: ...inspections in order to assess the condition of the fixed parts Rev A PROCEDURE FOR QUALITY CHECKS OF DR IEC ENTELLIGUARD G FAMILY Doc N 1SDH00XXXXX Page N DR KITS QUALITY CHECK PARAMETER FIXED PORTION PARTS ENTELLIGUARD T ENTELLIGUARD G MPACT MPACT PLUS ENTELLIGUARD L ENTELLIGUARD T ENTELLIGUARD G MPACT MPACT PLUS ENTELLIGUARD L ENTELLIGUARD T ENTELLIGUARD G MPACT MPACT PLUS ENTELLIGUARD L ENTELLI...

Страница 3: ...mage to devices or that could make them unsafe These warnings do not cover all the ways in which maintenance even if not recommended by ABB may be performed or the possible dangerous consequences that may arise from such actions Anyone who uses procedures and tools for maintenance whether it is recommended by ABB or not prescribed must make sure that his her own safety and that of the devices is n...

Страница 4: ...D G_FR2 _3P_3200A_4000A EMAX2 2 2 3P 20 N M ENTELLIGUARD G _FR2 _4P_3200A_4000A EMAX2 2 2 4P 25 N M MPACT_FR1 _3P_1600A EMAX2 2 2 3P 20 N M MPACT_FR1 _4P_1600A EMAX2 2 2 4P 20 N M MPACT_FR1 _3P_2500A EMAX2 2 2 3P 20 N M MPACT_FR1 _4P_2500A EMAX2 2 2 4P 20 N M MPACT_FR2 _3P_3200A_4000A EMAX2 2 2 3P 20 N M MPACT_FR2 _4P_3200A_4000A EMAX2 2 2 4P 25 N M ENTELLIGUARD L_FR1 _3P_1600A EMAX2 2 2 3P 20 N M...

Страница 5: ... grain sand paper 4 Make sure that the screws on the fixed part are properly tightened e g the screw that join the fixed part to the switchboard the ones that fasten the terminals of the fixed part to the switchboard bars and earthing plates 5 Check the non metallic secondary disconnect part and Front panel are not damaged and no crack is there 6 Make sure all the moving parts on the bottom of fixed p...

Страница 6: ... to assemble all parts related to Cradle 1SDH002090A1001 and follow the instructions as per mentioned Instruction sheet document Rev A PROCEDURE FOR QUALITY CHECKS OF DR IEC ENTELLIGUARD G FAMILY Doc N 1SDH00XXXXX Page N Visual Check gas Deflectors components to be assembled as per DR kit instruction sheet 06 17 ...

Страница 7: ...ne grain sand paper 4 Make sure that the screws on the fixed part are properly tightened e g the screw that join the fixed part to the switchboard the ones that fasten the terminals of the fixed part to the switchboard bars and earthing plates 5 Check the non metallic secondary disconnect part and Front panel are not damaged and no crack is there 6 Make sure all the moving parts on the bottom of fixed...

Страница 8: ...1 AND FR2 Visual Check Trip Free Assembly Contact Weld assembly anti insertion plates and associated components to be assembled as per DR kit drawing Fr1 3P Fr1 4P Visual Check Trip Free Assembly Contact Weld assembly anti insertion plates and associated components to be assembled as per DR kit drawing Fr2 3P Fr2 4P 08 17 ...

Страница 9: ...nd paper 4 Make sure that the screws on the fixed part are properly tightened e g the screw that join the fixed part to the switchboard the ones that fasten the terminals of the fixed part to the switchboard bars and earthing plates 5 Check the non metallic secondary disconnect part and Front panel are not damaged and no crack is there 6 Make sure all the moving parts on the bottom of fixed part are p...

Страница 10: ...r 4 Make sure that the screws on the fixed part are properly tightened e g the screw that join the fixed part to the switchboard the ones that fasten the terminals of the fixed part to the switchboard bars and earthing plates 5 Check the non metallic secondary disconnect part and Front panel are not damaged and no crack is there 6 Make sure all the moving parts on the bottom of fixed part are properly...

Страница 11: ...N 1SDH00XXXXX Page N ENTELLIGAUARD L FIXED PART FR1 Contact Weld Assembly Secondary disconnect Assembly Secondary disconnect Assembly Fig 1 3pole Fig 2 4pole to be changed as per DR kit drawing to be assembled as per DR kit drawing to be changed as per DR kit drawing 11 17 ...

Страница 12: ... Page N ENTELLIGAUARD L MPACT FIXED PART FR2 Trip Free Lever Aseembly Outer and inner guide has to assembled as depicted in drawing instruction sheet on both side Trip Free Lever Aseembly Outer and inner guide has to assembled as depicted in drawing instruction sheet on both side 12 17 ...

Страница 13: ...H00XXXXX Page N MPACT FIXED PART FR1 Trip Free Lever Aseembly Outer and inner guide has to assembled as depicted in drawing instruction sheet on both side Trip Free Lever Aseembly Outer and inner guide has to assembled as depicted in drawing instruction sheet on both side 13 17 ...

Страница 14: ...H00XXXXX Page N 1 VISUAL CHECK ON FIXED PORTION BEFORE LOADING THE BREAKER A Ensure that the front display panel of the cassette shows disconnected position as shown below 2 Visually check presence and proper mounting of all the parts and assemblies in the fixed portion as per instruction sheet DISCONNECT 14 17 ...

Страница 15: ... on the breaker are aligned properly as instructed in the Must ensure that the racking handle is not inserted before and during loading the breaker Handle should only be 3 RACK IN HANDLE NOT INSERTED BEFORE AND DURING LOADING THE BREAKER inserted when the breaker is pushed inside the cassette to dead end condition drawing or the instruction sheet 4 GREASE APPLICATION Visual check of grease applica...

Страница 16: ...REE WORKING IN BETWEEN TEST AND CONNECTED In between disconnected and connected condition charge the breaker try to put breaker to ON condition It should not be possible to ON the breaker in any circumstances Entelligaurd G all frames Entelligaurd L frame 1 3pole The breaker should trip before the racking handle is inserted in case of It should not be possible to insert the handle in case of Entel...

Страница 17: ...eaker Beaker will only be put to ON condition when handle is taken out Once the breaker is completely racked in connected position take out the handle and charge the breaker Put the breaker to ON condition and try to insert the racking handle It should not be possible to insert the handle Handle can only be inserted when breaker is in OFF condition CLUSTER ENGAGEMENT CHECK ON OFF operation must be...

Отзывы: