Endura AZ series integral and remote transmitter
Combustion oxygen monitor
4 Electrical Installation
IM/AZ20E–EN Rev. F
15
4.4 Remote Transmitter – Remote AZ10 Sensor Cable Connections
4.4.1 Systems with
5 m (
18 ft) Cable Length
Sensor connection
Transmitter Connection
Cable Color
Connection / Note
White / Yellow (not used)
White / Black (not used)
White / Orange (not used)
White / Green (not used)
White / Red (not used)
White / Blue (not used)
White / Yellow (not used)
White / Black (not used)
White / Orange (not used)
White / Green (not used)
White / Red (not used)
White / Blue (not used)
White / Yellow (not used)
White / Black (not used)
White / Orange (not used)
White / Green (not used)
White / Red (not used)
White / Blue (not used)
NOT USED
Cut wires back at
both ends of cable
Red
Red
Red
Cell + (oxygen input)
Black
Black
Black
Cell – (oxygen input)
Violet
Violet
Violet
ACJC
Grey
Grey
Grey
ACJC
Green
Green
Green
T/C +
White
White
White
T/C –
Earth stud (Screen 1 and 2)
SCN (not used)
Screen 1 and 2 (sleeved)
See Fig.
Brown
Brown
Brown
Heater 1
Blue
Blue
Blue
Heater 2
Table 4.1 Systems with
5 m (
18 ft) Cable Length
Fig. 4.4 Systems with
5 m (
18 ft) Cable Length
VIOLET
BLACK
RED
WHITE
CELL
–
+
–
+
GREY
GREEN
T/C
ACJC
CELL
T/C
–
+
+
R
W BL
BLUE
BROWN
GREEN
H1
CLR
CLR
H2
H1 H2
AZ10 sensor*
ACJ
C
(Gr
e
y
)
ACJ
C
(V
io
le
t)
TC+ (Gr
ee
n)
TC– (Whit
e
)
Cel
l +
(R
ed)
Cel
l – (Black)
Screen 1 and 2 drains connected to sensor
internal earth stud
only
– not to SCN terminal
AZ10 remote transmitter*
Cell + (Red)
Cell – (Black)
ACJC (Violet)
ACJC (Grey)
T/C + (Green)
T/C – (White)
NOT USED
SCN (Screen)
H (Blue) H (Brown)
H (Brown) H (Blue)
Not used – see Table 4.1
Screen 1 and 2 drains at sensor
connected to internal earth stud
only
Green (earth wire from
sensor earth stud)
Special ABB 14-core Cable Only:
5 m (
18 ft) Length
*Metal gland required at sensor and transmitter