NOTES
A.
The diagram indicates the connections for adaptation of EMAX E2.2-E4.2 series
circuit-breaker to GE M-PACT, GE M-PACT Plus, GEC ALSTHOM M-PACT,
Legrand
DMX, Legrand DPX, BTicino Megabreak, F.T.M.C. Power-WAVE Plus
series
withdrawable version circuit-breaker connectors in place of which it has to located.
For circuit of new EMAX E2.2-E4.2 series circuit-breaker see diagram
1SDM000091R0001.
For circuit of old GE M-PACT, GE M-PACT Plus, GEC ALSTHOM M-PACT
, Legrand
DMX, Legrand DPX, BTicino Megabreak, F.T.M.C. Power-WAVE Plus
series
circuit-breaker see corresponding catalogue.
C. Differential protection of old GE M-PACT, GE M-PACT Plus, GEC ALSTHOM M-PACT
,
Legrand DMX, Legrand DPX, BTicino Megabreak, F.T.M.C. Power-WAVE Plus
series circuit-breaker can be replaced by new EMAX 2 circuit breaker protection
with the use of UI/O homopolar current sensor on earth connection point.
D. For three poles circuit breaker: Rogowski coil on external neutral conductor of old
GE M-PACT, GE M-PACT Plus, GEC ALSTHOM M-PACT
, Legrand DMX, Legrand DPX,
BTicino Megabreak, F.T.M.C. Power-WAVE Plus
series circuit-breaker can be
replaced by UI/N current sensor of new EMAX 2 circuit breaker.
E.
With DR Direct Replacement solution maximum 6 auxiliary contacts available (3 nc
+ 3 no).
F.
In the presence of several Ekip Com modules, S75/5 contact should be connected
only once to a single module. If there are no carriage position contacts on the fixed
part of the old GE M-PACT, GE M-PACT Plus, GEC ALSTHOM M-PACT
, Legrand DMX,
Legrand DPX, BTicino Megabreak, F.T.M.C. Power-WAVE Plus
series circuit
breaker, the terminals 1-4 should be short-circuited.
G. In the presence of Ekip Cartridge accessory in Fig. 32, up to three applications
between Fig. 41…58 taken only once can be supplied.
The Ekip Com module selected can be duplicated, if required, by choosing between
Fig. 61…67.
H. Connect A17-A19 (PAMM) cables to W1 (Ekip Com Modbus) and A18-A20 (PAMM)
cables to W2 (Ekip Com Modbus) for switching from 4-wire Modbus communication
to 2-wire Modbus communication.