IEC/EN 60947-2 Annex M

0,5

0,3

1

1,5

2

3

0,5

0,4

0,3

0,2

0,1

0,06

0

Ι∆

n (A)

t (s)

ELR ID:

TR ID:

ON

FAULT

ALARM

TEST

off

tx10

Fault

Alarm

Ι∆

nx1

Ι∆

nx10

tx1

on

off

Ι∆

nx0,1

FAIL SAFE

ALARM

RESET

ELR72P

ON

FAU

LT

ALA

RM

8

2

5

6

7

*

ouput relays

V aux.

10

11

12

TRIP

ALARM

remote RESET

in current

test signal

current transf. TR...

1

3

9

13

14
15

16

4

I

x0,1

tx1

on

Fault

Alarm

I

x1

I

x10

tx10

off

FAIL SAFE

off

A

B

C

D

E

F

ALARM

1

0

72

80

 (with cover)

72

102

68

68

R3

62

9

12

67

ELR72P

*

Aux

3

2

1

4

5

6

7

8

9

10

11

12

13

14

15

16

ouput

relay

TRIP

ouput

relay

ALARM

V aux

input

current

remote

RESET

(auto reset)

out test

signal

T2-T1

S2-S1

2

3

4

1

ALIMENTAZIONE

TERRA

N L1 L2 L3

Ba

TR...

ELR72P

 

2CSG152424R1202

ELR72V24P

2CSG452424R1202

Front panel 

residual 

current relay

A Type 

Legenda:

1) - Sensitivity setting 

n

2) - Delay time setting
3) - Test pushbutton
4) - Reset pushbutton
5) - GREEN Led: auxiliary supply presence
6) - YELLOW Led: alarm contact intervention
7) - RED Led: trip contact intervention
8) - Terminals for auxiliary supply and toroidal connection 
9) - Terminals for output contacts connection

Auxiliary Power Supply

 

ELR72P: 110, 230, 400 V ac (±20%); 50-60 Hz

 

ELR72V24P: 24-48 V ac/dc (±20%); 50-60 Hz 

Maximum consumption 

4 VA

 

0,03 ÷ 0,3 A with K = 0,1

Sensitivity setting 

0,3 ÷ 3 A with K = 1

 

3 ÷ 30 A with K = 10

Delay time setting

 

0 ÷ 0,5 sec. with K = 1 

 

0,5 ÷ 5 sec. with K = 10

Signallings 

led ON, led ALARM, led FAULT

Alarm contact intervention 

60% I

Δ

n set

Toroidal transformers 

TR range

Output contact capacity 

5 A 250V

Adjustable features 

Autoreset, Alarm, Fail Safe, Remote reset

Operating temperature 

-10 ÷ 60°C

Storage temperature 

-20 ÷ 70°C

Max humidity 

≤ 

95 %

Dielectric test 

2,5 kV 60 sec.

Mounting position 

Any

Wiring type  

Screw terminals/ cross section cables 2,5 mm²

Protection degree

 

IP52 frontal with cover

 

(IP40 frontal) - IP20 terminals

Standard 

IEC EN 60947-2 Annex-M

Wiring diagram with shunt trip and Fail Safe OFF
Connect the terminals 10 and 11 when undervoltage release is used.

  A  -  Alarm function

 

  position 1: Alarm is OFF

 

  position 0: Alarm is ON

  B  -  Delay time multiplication constant

 

  position 1: K = 10

 

  position 0: K = 1

 C/D  -  Sensitivity multiplication constant

 

  c,d in position 0: K = 0,1

 

  c in position 1, d in position 0: K = 1

 

  c,d in position 1 K = 10

  E  -  Fail Safe (Trip Contact)

 

  position 1:  the relay is normally energized (Fail Safe)

 

  position 0:  the relay is normally de-energized

  F  -  Fail Safe (Alarm Contact)

 

  position 1:  the relay is normally energized (Fail Safe)

 

  position 0:  the relay is normally de-energized

Minidip

1

5

6

2

7

3

4

8

9

Auxiliary Power Supply Vaux:
ELR72P

•  Terminals 2 - 3 = 110 V ac (±20%)

•  Terminals 1 - 2 = 230 V ac (±20%)

•  Terminals 1 - 3 = 400 V ac (±20%)

ELR72V24P

•  Terminals 2 - 3 = 24 V ac/dc (±20%)

•  Terminals 1 - 3 = 48 V ac/dc (±20%)

Toroidal transformer connection:

-  To link terminals 7 and 8 with toroidal 
  terminals S1 and S2 (measure)
-  To link terminals 5 and 6 with toroidal 
  terminals T1 and T2 (test)

Remote reset / Autoreset:

-  To link terminals 15 and 16 with NO pushbutton 
  in order to realize remote reset function.
-  To link terminals 15 and 16 each other to 
  realize autoreset function.

Description

FRONT VIEW

REAR VIEW

Connection

Minidip Set Up

Technical features

Dimensions (mm)

EARTH

SUPPLY

SHUNT

TRIP

2CSG444008D51

02