Functions
IEC 60870-5-101 and IEC 60870-5-104
< c l e a r i e c 1 0 1 i n t e r f a c e { 1 | 2 } a t t a c h { c o n s o l e 0 |
< s e t i e c 1 0 1 i n t e r f a c e { 1 | 2 } l i n k a d d r e s s { 0 - 6 5 5 3 5 } >
< s e t i e c 1 0 1 i n t e r f a c e { 1 | 2 } l e n g t h l i n k - a d d r e s s { 0 - 2 } >
< s e t i e c 1 0 1 i n t e r f a c e { 1 | 2 } l i n k r e t r i e s { 0 - 1 0 } >
2.22.5
Configuration of an IEC 60870-5-104 Interface
If no IP address is set, any central office can connect with the device. If several interfaces are
configured without IP address then the active interface with the lowest number (n) always
connects.
If at least one IP address has been set then only the central office(s) with the configured IP
address(es) may connect. Four IP addresses per IEC 60870-5-104 interface are configurable
for central offices.
Commands to configure an IEC 60870-5-104 interface
< c l e a r i e c 1 0 4 i n t e r f a c e { 1 | 2 } a t t a c h r e m o t e - i p { I P
2.22.6
Configuration of the Time Monitor (Time-Out)
The protocols IEC 60870-5-101 and IEC 60870-5-104 use different timeout times to control the
establishment of a connection, acknowledment and retransmission. These are typically used
system-wide (central office and all remote control units) and do not have to be modified if
the values are accepted that are suggested by the standard. For time parameters and default
values refer to "Tab. 34: Time monitor counter".
Commands for configuring timeout for IEC 60870-5-101 / IEC 60870-5-104
< s e t { i e c 1 0 1 | i e c 1 0 4 } i n t e r f a c e { 1 | 2 } t i m e o u t { 0 - 3 }
Value for (t)
Description
0
The parameter sets the period between two connection
attempts.
The default value for IEC 60870-5-101 is: 1 s
The default value for IEC 60870-5-104 is: 30 s
1
Timeout for APDVs send.
The default value for IEC 60870-5-101 is: 3 s
The default value for IEC 60870-5-104 is: 15 s
2
Timeout for acknowledged in case of no data messages.
The default value for IEC 60870-5-101 is: 3 s
The default value for IEC 60870-5-104 is: 10 s
3
Inactivity counter for sending a test frame (TestFR, IEC
60870-5-104) or link test (IEC 60870-5-101).
The default value for IEC 60870-5-101 is: 3 s
Table 34: Time monitor counter
1KGT151021
V000 1
71
Содержание EDS500 Series
Страница 8: ...References Introduction 8 1KGT151021 V000 1 ...
Страница 152: ...Certificate Management Functions 152 1KGT151021 V000 1 ...
Страница 155: ...1KGT151021 V000 1 155 ...