26
EBS852 / EBS862
ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B
… 7 Electrical connections
Electrical data for inputs and outputs
Power supply
EBS852
Supply voltage (standard actuators)
115 V AC (94 to 130 V) or 230 V AC (190 to 260 V); 47.5 to 63 Hz; single-phase
Supply voltage (Ex actuators)
115 V AC (94 to 127 V) or 230 V AC (190 to 253 V); 47.5 to 63 Hz; single-phase
Average power loss P
avg
and power
consumption I
max
of the electronic unit
Actuator P
avg
l
max
at 115 V
l
max
at 230 V
l
pos
(115 V + 230 V):
approx. 40 to 50 % of l
max
RHD(E)250-10 60
W
1.8
A
0.9
A
RHD(E)500-10
75 W
2.2 A
1.1 A
RHD(E)800-10
60 W
5.0 A
2.5 A
RHD(E)1250-12
80 W
5.0 A
2.5 A
RHD(E)2500-25
80 W
5.0 A
2.5 A
RHD(E)4000-40
80 W
5.8 A
2.7 A
RHD(E)8000-80
80 W
5.0 A
2.5 A
RSD(E)10-5,0
55 W
2.2 A
1.1 A
RSD(E)10-10,0
60 W
3.6 A
1.8 A
RSD(E)20-5,0
60 W
3.6 A
1.8 A
RSD(E)20-7,5
75 W
4.8 A
2.4 A
RSD(E)50-3,0
75 W
5.0 A
2.5 A
RSD100-1.5
75 W
5.0 A
2.5 A
External fuse for electronic unit
16 A, time-lag
External fuse for heating (dewing protection)
2 to 6 A, medium time-lag
EBS862
Supply voltage (standard actuators)
230 V AC (190 to 260 V); 47.5 to 63 Hz; single-phase
Supply voltage (Ex actuators)
230 V AC (190 to 253 V); 47.5 to 63 Hz; single-phase
Average power loss P
avg
and power
consumption I
max
of the electronic unit
Actuator P
avg
l
max
at 230 V
l
pos
(230 V):
approx. 40 to 50 % of l
max
RHD(E)2500-10 80
W
5.3
A
RHD(E)4000-10 100
W
10.0
A
RHD8000-12 115
W
8.0
A
RHDE8000-15 115
W
8.0
A
RHD(E)16000-30 115
W
12.5
A
RSD(E)50-10,0 100
W
6.4
A
RSD100-10.0 115
W
12.5
A
External fuse for electronic unit
Safety fuse 35 A (Lindner) + thermal circuit breaker 16 A (ETA)
(fuses are in the scope of delivery)
External fuse for heating (dewing protection)
2 to 6 A, medium time-lag