![ABB DNP 670 Series Скачать руководство пользователя страница 28](http://html.mh-extra.com/html/abb/dnp-670-series/dnp-670-series_communication-protocol-manual_4667028.webp)
•
Variation 1 - 32-bit with flag
•
Variation 2 - 16-bit with flag
•
Variation 3 - 32-bit without flag
•
Variation 4 - 16-bit without flag
•
Variation 5 - single-precision floating point with flag
•
Variation 6 - double-precision floating point with flag
The IED supports all 32-bit and floating point variants without any additional scaling
configuration. This is given as long as the
MaxSourceVal
(as it is given in the IED as
floating point) is in the range of a 32-bit signed integer value (max. 32-bit = 2 147 483
648).
Section 3
1MRK 511 391-UUS A
Vendor-specific implementation
22
670 series 2.2 ANSI
Communication protocol manual