17
Note:
The RC / snubber circuit could also cause 0
Ω
result for a short time.
The measurement, showing less resistance than 1
Ω
should be made a second time with test leads applied to
the terminals with opposite polarity; if this measurement shows the same result, one or two thyristors located
in that path are faulty; they need to be replaced.
Standard thyristor power controllers size T5 (890 A … 960 A), wS500
Standard thyristor power controllers, wS500. Internal semiconductor fuses are included.
−
The thyristor power controller must be disconnected from the mains.
Blown fuses
−
Using the OHM function of a normal multimeter, measurements must be made from both sides of the
semiconductor fuses (e.g. U1 to thyristor, V1 to thyristor and W1 to thyristor):
Faulty thyristor
−
Make sure, the internal fuses are fine.
−
Using the OHM function of a normal multimeter, measurements must be made from both sides of the
thyristor power controller (e.g. U1 to U2, V1 to V2 and W1 to W2).
−
Normally, each measurement should show high resistance (> 1 k
Ω
).
−
Target: find a short circuit, indicated by low resistance (< 1
Ω
) (destroyed thyristor).
−
If the Thyristor power controller is designed with thyristor modules, then a module consists of two
thyristors. In this case, it is sufficient to know which thyristor module has a defective thyristor because the
complete module must be replaced.
−
After a thyristor module is replaced, the above-mentioned measurement should be done another time to
make sure that all faulty thyristors have been detected!
Note:
The RC / snubber circuit could also cause 0
Ω
result for a short time.
The measurement, showing less resistance than 1
Ω
should be made a second time with test leads applied to
the terminals with opposite polarity; if this measurement shows the same result, one or two thyristors located
in that path are faulty; they need to be replaced.
Thyristor power controllers size T1 … T4 (20 A ... 740 A), with +S500
Thyristor power controllers, with +S500. Internal semiconductor fuses are included.
−
The thyristor power controller must be disconnected from the mains.
Fault Tracing Thyristors
3ADW000449R0101 DCT880 Service Manual e a
Содержание DCT880
Страница 1: ...DCT880 Service Manual DCT880 Thyristor power controller 20 A 4160 A ...
Страница 2: ......
Страница 85: ...85 T2 160 A 245 A Appendix A Spare Parts List 3ADW000449R0101 DCT880 Service Manual e a ...
Страница 86: ...86 T3 325 A 420 A Appendix A Spare Parts List 3ADW000449R0101 DCT880 Service Manual e a ...
Страница 87: ...87 T4 550 A 740 A Appendix A Spare Parts List 3ADW000449R0101 DCT880 Service Manual e a ...
Страница 88: ...88 T5 890 A 960 A Appendix A Spare Parts List 3ADW000449R0101 DCT880 Service Manual e a ...