H4T hardware
3ADW000803R0101 DCS880 H4T (Tosa) manual en a
Galvanic isolation - T90, A92, F11, F90
The Galvanic isolation is an option for converters size H4T, H6 ... H8 and rated voltages ≤ 1000 V.
It is used to replace the high-ohmic voltage measurement and gives the advantage of a total isolation
between power part and drive electronics.
The transformer T90 and the DC-DC transducer A92 are located outside the converter module. The
internal AC and DC voltage measurement channels are removed and connected to T90 and A92.
Voltage coding
Size
H4T
Unit nominal voltage [V]
U1 [V
AC
]
①
c = 7 (690 V)
c = 8 (800 V)
Rated mains voltage [V
AC
]
315 ... 690
360 ... 800
Voltage measurement scaled by type code or parameter
(95.28)
690
800
Measuring board
SDCS-PIN-H51 use connector X15
Galvanic isolation
Fuse
F11
1500 V, 5 A
DC-DC transducer
A92
P42000D3-0111 (3ADN260008P0001)
Switch position R
G
2
(945 V)
3
(1080 V)
Fuse
F90
1000 V, 10 A
Transformer
T90
3ADT745047P0001
Secondary Terminals
2U3
2V3
2W3
2N
2U4
2V4
2W4
2N
①
Rated voltage see the name plate of the unit.