![ABB DCS800 Скачать руководство пользователя страница 23](http://html.mh-extra.com/html/abb/dcs800/dcs800_installation-manual_3333023.webp)
23
Holes inside the cabinet
The cabinet can be fastened to the floor using the fastening holes inside the
cabinet, if they are available and accessible. Allowed maximum distance between
the fastening points is 800 mm.
Fastening holes inside the cabinet
Side plates of the cabinet: 15 mm
Back plate of the cabinet: 10 mm
Small gap between the 200 mm, 400 mm, 600
mm, 800 mm, 1000 mm and 1500 mm cabinets:
25
Fastening holes
Gap between cabinets
Fastening hole distances for the common cabinet are given in
Fastening bolt: M10 to M12 (3/8” to 1/2”).
Cabinet Width
(mm)
Hole Distance (mm)
200 a:
50
400 a:
250
600 a:
450
800 a:
650
1000
a: 350, b: 150, a: 350
1500
a: 350, b: 150, a: 350, b: 150, a: 350
Hole distances
The bottom plate subassemblies / frames of most cabinets (layout see next pages)
are equipped with mounting holes (
∅
18.5 mm) together with trough holes (
∅
31
mm).
a
Mechanical Installation
3ADW000352R0101 DCS800-A Installation Manual e a