Terminal Numbers 

 Klemm-nummer

 

Description 

 

 

93, 94 

Power 24 V AC/DC 

Important

: The common power connection (terminal 33) must be connected to Earth. ABB Cylon 

recommend that this is done at the 24 V AC transformer. 

 

 

95, 96 

RS-485 Port 1 (BACnet® MS/TP or Modbus RTU) screw terminal 

MS/TP subnet terminator switch is located beside the port. If the switch is towards the   icon, then 

termination is 

in

 and if the switch is towards the  icon then termination is 

out

 

 

39 … 42

 

Sensor / RS-485 Port 2 (Cylon® room sensors or BACnet® MS/TP or Modbus RTU) 

The bus Terminator Switch is located beside the port. If the switch is towards the   icon, then 

termination is 

in

 and if the switch is towards the  icon then termination is 

out

 
 

 

 

 

 

 

 

 

 

 

 

Description

 

 

 

 

Ethernet Ports 

 

 

USB ports 

Used for firmware upgrade 

 

 

 

 

Indicator LEDs 

 

  

Off 

On 

Slow Blink 

Fast blink 

 

Red LED 

(Power) 

Power is off 

Power is on 

___  Unit Rebooting  ___ 

 

Green LED

 

(Status) 

Unit is not 

running 

Strategy Loaded 

but no network 

connectivity 

Strategy Loaded and 

device communicating 

on network 

No Strategy 

loaded 

 

Yellow LED 

(FLX) 

FLX bus comms 

are ok 

No FLX bus comms 

FLX bus address clash 

FLX bus 

comms error 

During firmware upgrade over IP network, the Yellow LED will remain on while the strategy/comms section reboots, and then the LEDs will rotate 

Red-Green-Yellow while the IO section reboots. 

Note

:  During typical operation, the Red 

LED should be on, the Green LED 

should be blinking and the Yellow 

LED should be off. 

 

 

 

 

Push buttons and Signal LEDs 

Reset to Factory default IP/Password :  while the controller is 

running

, press 

SW1

 until LED 

L2

 lights up, then release 

SW1

Restart the controller:  while the controller is 

running

, press 

SW2

 until LED 

L2

 lights up, then release 

SW2

.

 

Factory Reset  

(Reset to default Factory settings including, Shipped version of firmware, wipe strategy data, and reset IP/Password)

:  while the 

controller is 

booting

 hold  

SW1

 until LED

 L2

 lights up, then release 

SW1

.  

LED

 

L2 

will indicate the progress as shown in 

L1

/

L2

 signals below.

 

USB upgrade: insert a FAT-formatted USB drive containing valid firmware (.swu) into either of the USB ports, while the controller is 

booting

 

hold  

SW1

 until LED

 L1

 lights up, then release 

SW1

.  

LED

 

L1 

will indicate the progress as shown in 

L1

/

L2

 signals below.

 

LED 

L1

 / LED 

L2

 signals 

 

Slow blink:       Upgrade / Reset in progress 

 

Solid colour:  Upgrade / Reset successful.   

Power-cycle the controller to activate. 

 

Fast blink 

Upgrade /Reset failed 

 

 

 

Inter-module connection sockets 

To join the 

FLX bus

, place the devices side-by-side and place the 

FLX bus connector

 into the two adjacent sockets at once. 

The end device on a 

FLX bus

 (either a 

FLX

 device or the 

FBXi

 itself) must have a terminator inserted into its interconnector 

socket. One terminator is shipped with each 

FBXi

 device. 

 