41-222.2J

Type CP Reverse Phase Relay

4

tor switch (when supplied) will carry this current long
enough to trip a circuit breaker.

The indicating contactor switch (when supplied) has
two taps that provide a pickup setting of 0.2 or 2
amperes. To change taps requires connecting the
lead located in front of the tap block to the desired
setting by means of a screw connection.

TRIP CIRCUIT CONSTANT

Indicating contactor switch (ICS) (When Supplied).

0.2 ampere tap -  -  -  -  -  -  - 6.5 ohms d-c resistance
2.0 ampere tap -  -  -  -  -  -  0.15 ohms d-c resistance

INDICATING VOLTAGE SWITCH (IVS) 

(WHEN SUPPLIED)

The indicating voltage switch (IVS) has a series
resistor. The IVS will operate when 80% d-c rated
voltage is applied to the IVS circuitry.

4.0

INSTALLATION

The relays should be mounted on switchboardsepa-
rated to allow for a minimum contact gap of panels or
their equivalent in a location free from dirt, moisture,
excessive vibration and heat.

Mount the relay vertically by means of the rear
mounting stud or studs for the type FT projection
case or by means of the four mounting holes on the
flange for the semi-flush type FT case. Either the
stud or the mounting screws may be utilized for
grounding the relay. External toothed washers are
provided for use in the locations shown on the outline
and drilling plan to facilitate making a good electrical
connection between the relay case, its mounting
screws or studs, and the relay panel. Ground wires
should be affixed to the mounting screws or studs as
required for poorly grounded or insulating panels.
Other electrical connections may be made directly to
the terminals by means of screws for steel panel
mounting or to the terminal stud furnished with the
relay for thick panel mounting. The terminal stud may
be easily removed or inserted by locking two nuts on
the stud and then turning the proper nut with a
wrench.

For detail information on the FT case refer to Instruc-
tion Leaflet 41-076.

5.0

SETTINGS

There are two independent relay adjustments. These
are the high and low voltage contact settings as
described under “Characteristics”. These settings
determine the balanced three phase line-to-line
voltage at which the relay contacts trip. The relay
timing is not an independent adjustment, since it is
fixed by the contact settings chosen. Typical time
curves for various contact settings are given in Figs.
6 and 7.

For motor protection set the low-voltage contact at
the minimum permissible operating voltage. (This
contact may also close when the motor is operated
single-phased, provided the open phase voltage is
not held too close to normal by the motor. A motor
operating near full load or a motor connected in par-
allel with substantial static load will not be able to
maintain near normal open-phase voltage.) Where
the high voltage contact supervises supply breaker
closing, it must be set lower than normal voltage. For
example, set the high-voltage contact at 90% and the
low-voltage contact at 80% of rated voltage. The high
and low-voltage contacts must be sufficiently sepa-
rated to allow for a minimum contact gap of about
0.020 inch. This corresponds to a voltage setting
separation of about 7%.

Fig. 5.

Internal Schematic of the Type CP Relay with Indi-
cating Contactor Switch in the High Voltage Circuit
in the Type FT-11 Case.

183A961

Sub 1

*

Содержание CP Series

Страница 1: ......

Страница 2: ...41 222 2J Type CP Reverse Phase Relay 2 Sub 5 184A202 Fig 2 Internal Schematic of the Type CP Relay with Independent Contacts in the Type FT 11 Case Fig 1 Type CP Relay Without Case ...

Страница 3: ...able high and low voltage contacts which can be set around the periph ery of a scale The ranges of adjustment of the con tacts are as follows 120 volt relay 70 to 120 volts 240 volt relay 140 to 240 volts 480 volt relay 280 to 480 volts 208 volt relay 120 to 220 volts If either of the adjustable contacts are set for a value of voltage within these ranges the relay will just close its contacts when...

Страница 4: ... connections may be made directly to the terminals by means of screws for steel panel mounting or to the terminal stud furnished with the relay for thick panel mounting The terminal stud may be easily removed or inserted by locking two nuts on the stud and then turning the proper nut with a wrench For detail information on the FT case refer to Instruc tion Leaflet 41 076 5 0 SETTINGS There are two...

Страница 5: ...ts to insure correct operation of this relay have been made at the factory Upon receipt of the relay no adjustments other than those covered under Settings should be required ACCEPTANCE CHECK The following check is recommended to insure that the relay is in proper working order A CP UNIT 1 Contacts Set the left hand adjustable contact in the center of the scale and adjust the voltage until the mov...

Страница 6: ...drop freely 6 1 ROUTINE MAINTENANCE All relays should be inspected periodically and the time of operation should be checked at least once every year or at such other time intervals as may be dictated by experience to be suitable to the particular application All contacts should be periodically cleaned A contact burnishes S 182A836HO1 is recommended for this purpose The use of abrasive material for...

Страница 7: ...For the 240 volt relay multiply these values by two Similarly for the 480 volt relay multiply these values by four For the 208 volt relay set the high voltage contact on 170 volts and the low voltage contact on 120 volts Apply rated voltage and frequency to the relay to allow the high voltage contact to make Suddenly drop the voltage to zero and adjust the permanent magnet gap until the relay oper...

Страница 8: ...ve Phase 3 Phase 3 or 4 Wire S P D T with ac Independent Voltage Switch in Type FT 11 Case Fig 11 Relay Type CP Reserve Phase 3 Phase 3 or 4 Wire S P D T Contacts with Indicating ac Contactor Switch in Low Voltage Circuit in Type FT 11 Case Sub 1 184A469 Sub 1 184A836 ...

Страница 9: ...Type CP Reverse Phase Relay 41 222 2J 9 Fig 12 External Schematic Diagram of the Type CP Relay in the Type FT 11 Case Sub 1 184A200 ...

Страница 10: ... 222 2J Type CP Reverse Phase Relay 10 Fig 13 Relay Type CP Reverse Phase 3 Phase 3 or 4 S P D T with A C S in Low Voltage Circuit and with A C Independent Voltage Switch in Type FT 11 Case Sub 3 879A900 ...

Страница 11: ......

Страница 12: ...ABB Inc 4300 Coral Ridge Drive Coral Springs Florida 33065 Telephone 1 954 752 6700 Fax 1 954 345 5329 www abb com substation automation IL 41 222 2 Revision J ABB ...

Отзывы: