41-116.1C

2

COV Voltage Controlled Overcurrent Relay

duced by the electromagnet result in out-of-phase
fluxes in the air gap. The out-of-phase air gap fluxes
produced cause a contact closing torque.

2.2

VOLTAGE UNIT (V)

The voltage unit is an induction type cylinder type
unit.

Mechanically, the voltage unit is composed of four
basic components: A die-cast aluminum frame, an
electromagnet, a moving element assembly, and a
molded bridge.

The frame serves as the mounting structure for the
electromagnet and for a magnetic core. The mag-
netic core houses the lower pin bearing and is
secured to the frame by a locking nut. The bearing
can be replaced if necessary, without having to
remove the magnetic core from the frame.

The electromagnet has two pairs of voltage coils.
Each pair of diametrically opposed coils is connected
in series. In addition, one pair is in series with an
adjustable resistor. These sets are paralleled as
shown in Figure 2, page 11. The adjustable resistor
serves not only to shift the phase angle of the one
flux with respect to the other to produce torque, but it
also provides a dropout adjustment.

Locating pins in the electromagnet are used to accu-
rately position the lower pin bearing, which is
mounted on the frame, with respect to the upper pin
bearing, which is threaded into the bridge. The elec-
tromagnet is secured to the frame by four mounting
screws.

The moving element assembly consists of a spiral
spring, contact carrying member, and an aluminum
cylinder assembled to a molded hub which holds the
shaft. The shaft has removable top and bottom jewel
bearings. The shaft rides between the bottom pin
bearing and the upper pin bearing with the cylinder
rotating in an air gap formed by the electromagnet
and the magnetic core. The stops for the moving ele-
ment contact arm are an integral part of the bridge.

The bridge is secured to the electromagnet and
frame by two mounting screws. In addition to holding
the upper pin bearing, the bridge is used for mount-
ing the adjustable stationary contact housing. The
stationary contact housing is held in position by a
spring type clamp. The spring adjuster is located on
the underside of the bridge and is attached to the
moving contact arm by a spiral spring. The spring
adjuster is also held in place by a spring type clamp.

With the contacts closed, the electrical connection is

made through the stationary contact housing clamp,
to the moving contact, through the spiral spring out to
the spring adjuster clamp.

2.3

INDICATING CONTACTOR SWITCH UNIT 
(ICS)

The indicating contactor switch is a small dc oper-
ated clapper type device. A magnetic armature, to
which leaf-spring mounted contacts are attached, is
attracted to the magnetic core upon energization of
the switch. When the switch closes, the moving con-
tacts bridge two stationary contacts, completing the
trip circuit. Also during this operation two fingers on
the armature deflect a spring located on the front of
the switch, which allows the operation indicator target
to drop. The target is reset from the outside of the
case by a push rod located at the bottom of the
cover.

The front spring, in addition to holding the target, pro-
vides restraint for the armature and thus controls the
pickup value of the switch.

3.0

CHARACTERISTICS

To prevent the relay from operating for currents
above the overcurrent unit pickup, the voltage unit
contact is connected to control the telephone relay
whose contacts are connected in the shading coil cir-
cuit of the overcurrent unit. The voltage contact is
held open at voltage above the set point, to prevent
torque from being produced in the overcurrent unit.
This arrangement yields a tripping characteristic as
shown in Figure 3, page 12.

3.1

OVERCURRENT UNIT

The relays are generally available in the following
overcurrent unit ranges:

These relays may have either single or double circuit
contacts for tripping either one or two circuit break-
ers.

The time vs. current characteristics are shown in Fig-
ures 4 to 8, starting on page 13. These characteris-
tics give the contact closing time for the various time
dial settings when the indicated multiples of tap value
current are applied to the relay

3.2

VOLTAGE UNIT

The contacts can be adjusted to close and energize

RANGE

TAPS

0.5 - 2.5

2 - 6

4 - 12

0.5

0.6

0.8

1.0

1.5

2.0

2.5

2

2.5

3

3.5

4

5

6

4

5

6

7

8

10

12

Содержание COV-6

Страница 1: ...ave been specially designed and tested to establish their suitability for Class 1E appli cations in accordance with the ABB Relay Division program for Class 1E Qualification Testing as detailed in Bul...

Страница 2: ...g is held in position by a spring type clamp The spring adjuster is located on the underside of the bridge and is attached to the moving contact arm by a spiral spring The spring adjuster is also held...

Страница 3: ...ll respond to multi ples of tap value currents in accordance with the var ious typical time current curves The factory adjustment of the CO unit contacts provides a contact follow Where circuit breake...

Страница 4: ...By turning the time dial move the moving contacts until they deflect the stationary con tact to a position where the stationary contact is resting against its backstop The index mark located on the m...

Страница 5: ...er trips and the target drops Then release the contacts and observe that the reset is smooth and positive If an additional time check is desired pass second ary current through the relay and check the...

Страница 6: ...ntil the operation time corresponds to the value of Table 1 For type COV 11 relay only the 1 30 times tap value operating time from the number 6 time dial position is 54 9 5 seconds It is impor tant t...

Страница 7: ...pedestal and moving the ICS in the downward position a Contact Wipe Adjust the stationary contact so that both stationary contacts make with the moving contacts simultaneously and wipe 1 64 to 3 64 w...

Страница 8: ...Y REQUIREMENTS COV 7 OVERCURRENTS UNITS Ampere Range Tap Continuous Rating Amperes One Second Rating Amperes Power Factor Angle Volt Amperes At Tap Value Current At 3 Times Tap Value Current At 10 Tim...

Страница 9: ...Range Tap Continuous Rating Amperes One Second Rating Amperes Power Factor Angle VOLT AMPERES At Tap Value Current At 3 Times Tap Value Current At 10 Times Tap Value Current At 20 Times Tap Value Cur...

Страница 10: ...COV Voltage Controlled Overcurrent Relay Telephone Relay T Overcurrent Unit CO Indicating Contactor Switch ICS Figure 1 Type COV Relay without case 1342D82A01 Photo Voltage Unit Adjustable Resistor Vo...

Страница 11: ...41 116 1C 11 COV Voltage Controlled Overcurrent Relay Sub 6 3526A40 Figure 2 Internal Schematic of the Type COV Relay in the Type FT 21 Case For Class 1E Application...

Страница 12: ...NORMAL CURRENT IN PERCENT OF FULL LOAD The Trip Area May be Changed as Follows The line bc may be moved in the direction of arrow y by changing the voltage unit setting The line ab may be moved in the...

Страница 13: ...41 116 1C 13 COV Voltage Controlled Overcurrent Relay Figure 4 Typical 50 and 60 hertz Time Curves of COV 6 Overcurrent Unit 619511 Sub 1...

Страница 14: ...41 116 1C 14 COV Voltage Controlled Overcurrent Relay Figure 5 Typical 50 and 60 hertz Time Curves of COV 7 Overcurrent Unit 619512 Sub 1...

Страница 15: ...41 116 1C 15 COV Voltage Controlled Overcurrent Relay Figure 6 Typical 50 and 60 hertz Time Curves of COV 8 Overcurrent Unit 619513 Sub 1...

Страница 16: ...41 116 1C 16 COV Voltage Controlled Overcurrent Relay Figure 7 Typical 50 and 60 hertz Time Curves of COV 9 Overcurrent Unit 619514 Sub 1...

Страница 17: ...41 116 1C 17 COV Voltage Controlled Overcurrent Relay Figure 8 Typical 50 and 60 hertz Time Curves of COV 11 Overcurrent Unit 619515 Sub 1...

Страница 18: ...41 116 1C 18 COV Voltage Controlled Overcurrent Relay Figure 9 Diagram of Test Connections of COV Relays 1582C85 Sub 6...

Страница 19: ...41 116 1C 19 COV Voltage Controlled Overcurrent Relay Figure 10 External Schematic of the COV Relay on a Generator Sub 2 3531A56...

Страница 20: ...S A ABB Automation Inc 4300 Coral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 visit our website at www abbus com papd Figure 11 Outline and Drilling Plan for the Type COV...

Отзывы: