Installation
10 - EN
CoriolisMaster FCM2000
CI/FCM2000-EN
4.1.2 Electrical connections between the transmitter and the peripherals
Input and output signals, supply power ME2/MS2
G00813
31 32 33 34 51 52 41 42 81 82
N
2-
L
1+
6
7
5
4
3
2
1
51 52 81 82 41 42 31 32 33 34
3
7
7
2
6
5
4
N
2-
L
1+
1
ME22
ME23
ME24
ME25
7
7
MS21
ME27
ME28
MS26
7
Fig. 3
1
Supply power
Line voltage: U
AC
100 ... 230 V AC, frequency 50/60 Hz,
terminals L, N,
Low voltage: U
AC
24 V, frequency 50/60 Hz, terminals 1+, 2-
Low voltage:
U
DC
24 V
2
Current output 1: can be selected via software
2a: function: active
Terminals: 31, 32; 0/4 … 20 mA (0
Ω
≤
R
B
≤
560
Ω
, ME27/28: 0
Ω
<= RB <= 300
Ω
)
2b: alternate function: passive (option D)
Terminals: 31, 32; 4 ... 20 mA (0
Ω
≤
R
B
≤
600
Ω
)
Source voltage 12
≤
U
q
≤
30 V
3
Current output 2: can be selected via software
Function:
passive
Terminals: 33, 34; 4 … 20 mA (0
Ω
≤
R
B
≤
600
Ω
)
Source voltage 12
≤
U
q
≤
30 V
4a Passive pulse output, terminals: 51, 52
f
max
= 5 kHz, pulse width 0.1 … 2,000 ms
Setting range: 0.001 … 1,000 pulses/unit
"Closed": 0 V
≤
U
CEL
≤
2 V, 2 mA
≤
I
CEL
≤
65 mA
"Open": 16 V
≤
U
CEH
≤
30 V, 0 mA
≤
I
CEH
≤
0.2 mA
4b Active pulse output
U = 16 ... 30 V, load
≥
150
Ω
, f
max
= 5 kHz,
5
Contact output, passive
Terminals: 41, 42
"Closed": 0 V
≤
U
CEL
≤
2 V, 2 mA
≤
I
CEL
≤
65 mA
"Open": 16 V
≤
U
CEH
≤
30 V, 0 mA
≤
I
CEH
≤
0.2 mA
6
Contact input, passive
Terminals: 81, 82
"On": 16 V
≤
U
KL
≤
30 V
"Off": 0 V
≤
U
KL
≤
2 V
7
"PA" equipotential bonding. When transmitter ME2 is connected
to flowmeter sensor MS26, transmitter ME2 also has to be
connected to "PA".
Important
An additional document with Ex safety instructions is available for measuring systems that are
used in explosion hazardous areas (Applies to FM / CSA only).
As a result, it is crucial that the specifications and data it lists are also observed.