5

2

ELECTRICAL INSTALLATION

Fig. 2.4 OPTO22 Board Connections

2.6

Serial Connections – Figs. 2.1 to 2.4

Information.

Up to 

10 slaves 

can be connected to a single 

RS422

 

adaptor card on a PC.

Up to 

32 slaves

 can be connected to a single 

RS485

 

adaptor card on a PC.

The number of slaves can be increased if the driver's serial port permits.

Connections to the MODBUS serial board must be made as shown in Figs. 2.1, 2.2 or 2.4.
Connections on links with multiple slaves must be made in parallel, as shown in Fig. 2.3. When
connecting cable screens, ensure that no 'ground loops' are introduced.

The maximum serial data transmission line length for both 

RS422 

and 

RS485

 

systems is 1200m. The types

of cable that can be used are determined by the total line length:

Up to 6m

– standard screened or twisted pair cable.

Up to 300m

– twin twisted pair with overall foil screen and an integral drain wire, e.g. Belden 9502

or equivalent.

Up to 1200m

– twin twisted pair with separate foil screens and integral drain wires, e.g. Belden

9729 or equivalent.

Rx+

Rx–

C500

Tx+

GND

Rx+

Rx–

Tx+

Tx–

GND

OPTO22 Adaptor

Board Connections

Screen

Tx–

8

9

4

5

3

32
33
34
35
36

Содержание COMMANDER 500

Страница 1: ...ABB Instrumentation COMMANDER 500 User Guide MODBUS Serial Communications 50 5 15 0 COMMANDER 500 50 1...

Страница 2: ...be stored away from heat protected from temperature extremes and powders kept dry Normal safe handling procedures must be used 6 When disposing of chemicals ensure that no two chemicals are mixed Saf...

Страница 3: ...Code 06 13 5 5 Loopback Test Function Code 08 14 5 6 Force Multiple Coils Function Code 15 15 5 7 Write Multiple Registers Function Code 16 16 6 EXCEPTION RESPONSES 17 6 1 Examples 17 7 ADDRESSABLE PA...

Страница 4: ...d with the instrument Information The MODBUS option provides the following facilities Standard RS422 485 communications MODBUS RTU protocol for master host computer to slave COMMANDER 500 system Isola...

Страница 5: ...immunity to noise pick up 2 2 OPTO22 Boards for use with Personal Computers Where a personal computer is used as the host computer the following OPTO22 boards are recommended for use with the COMMANDE...

Страница 6: ...Pull up and Pull down Resistors Four wire Operation Host Computer 5V 0V A B 1 8k Pull down Resistor 1 8k Pull up Resistor 0V 5V 0V A B 1 8k Pull down Resistor 1 8k Pull up Resistor Rx Rx Tx Tx C 32 3...

Страница 7: ...ust be made in parallel as shown in Fig 2 3 When connecting cable screens ensure that no ground loops are introduced The maximum serial data transmission line length for both RS422 and RS485systems is...

Страница 8: ...MMANDER 500 must be configured with the correct serial transmission parameters and assigned a unique address 3 1 Accessing the Serial Configuration Displays 450 2 500 0 70 xxxx COdE 50 AtNE LEV2 LEV5...

Страница 9: ...or a few seconds Serial Configuration 0 OFF 1 2 wire connection 2400 baud rate 2 4 wire connection 2400 baud rate 3 2 wire connection 9600 baud rate 4 4 wire connection 9600 baud rate 5 2 wire connect...

Страница 10: ...tween 1 and 99 A broadcast address address zero can be used to write to all slave devices simultaneously using one command In this instance there is no slave acknowledgment Slaves cannot accept new me...

Страница 11: ...A M M O C e h T t n i o p n a e l o o B e t e r c s i d e n o e t i r W e l b a e t i r w y l t n e r r u c t o n s i 6 0 e l g n i S t e s e r P r e t s i g e R e r o f e b r e t s i g e r e h t o t...

Страница 12: ...1 2 Read Coil Status Response The data is packed one bit for each coil 1 ON 0 OFF The response includes the slave address function code quantity of data characters the data characters and error check...

Страница 13: ...ressed slave responds with its address and function code followed by the information field The information field contains one byte describing the quantity of data bytes to be returned Two bytes are us...

Страница 14: ...use of slave address zero broadcast mode forces all attached slaves to modify the desired coil Example Switch ON coil address 39 auto manual state in slave 01 5 3 2 Force Single Coil Response The res...

Страница 15: ...an the register number must be used e g to write to register 104 the offset address 103 67H is transmitted 5 4 2 Preset Single Register Response The response to a Preset Single Register Response reque...

Страница 16: ...owed by two bytes to designate the action to be taken Example 5 5 2 Loopback Test Response The Loopback Test Response always echoes the query only diagnostic code 0 bytes 3 and 4 can be used Example s...

Страница 17: ...coil 39 to ON Select manual mode and coil 40 to OFF Select Local Set Point mode 5 6 2 Force Multiple Coils Response The Force Multiple Coils Response confirms slave identification function code start...

Страница 18: ...he value 100 to the register address 105 integral action time in slave 01 5 7 2 Write Multiple Registers Response The Write Multiple Registers Response confirms slave identification function code star...

Страница 19: ...V a t a D l a g e l l I e h t n o e l b a w o l l a t o n s i d l e i f a t a d e h t n i d e c n e r e f e r e u l a v e h T n o i t a c o l e v a l s d e s s e r d d a 7 0 e v i t a g e N t n e m e...

Страница 20: ...t a t s 5 A e g d e l w o n k c a m r a l A R e v i t c A 1 3 2 e t a t s 6 A e g d e l w o n k c a m r a l A R e v i t c A 1 4 2 e t a t s 7 A e g d e l w o n k c a m r a l A R e v i t c A 1 5 2 e t...

Страница 21: ...d a e R s e u l a V s t i m i L 0 2 V P R 9 9 9 9 o t 9 9 9 1 2 t n i o p t e s l o r t n o C R 9 9 9 9 o t 9 9 9 2 2 t a e H 1 t u p t u O W R 0 0 0 1 o t 0 0 0 0 1 o t 0 0 g n i t n e s e r p e r 3...

Страница 22: ...0 0 0 1 o t 0 0 g n i t n e s e r p e r 0 0 0 1 o t 0 3 4 2 t u p t u O W R 0 0 0 1 o t 0 0 g n i t n e s e r p e r 0 0 0 1 o t 0 4 4 e l b a i r a v e c n a b r u t s i D R 0 0 0 1 o t 0 0 g n i t n...

Страница 23: ...g n i t n e s e r p e r 0 0 0 1 o t 0 8 7 n i a g d r a w r o f d e e F W R 9 9 9 9 o t 1 0 9 7 s a i b d r a w r o f d e e F W R 0 0 0 1 o t 0 0 0 1 0 0 0 1 o t 0 0 0 1 g n i t n e s e r p e r s e u...

Страница 24: ...r 9 9 9 9 o t 0 3 9 e m i t g n i l t t e S R s d n o c e s 9 9 9 9 o t 0 4 9 l a r g e t n i r o r r E R s t i n u g n e n i 9 9 9 9 o t 0 r e t s i g e R o N l e b a L e l b a i r a V e t i r W d a...

Страница 25: ...W R 9 9 9 9 o t 1 0 5 0 1 1 e m i t n o i t c a l a r g e t n I W R 0 0 2 7 o t 0 6 0 1 1 e m i t n o i t c a e v i t a v i r e D W R 9 9 9 9 o t 0 0 7 0 1 e u l a v t e s e r l a u n a M W R 0 0 0 1...

Страница 26: ...o t 9 9 9 2 3 1 s i s e r e t s y h 1 A m r a l A W R s t i n u g n e n i 9 9 9 9 o t 0 3 3 1 s i s e r e t s y h e m i t 1 A m r a l A W R s d n o c e s 9 9 9 9 o t 0 4 3 1 e p y t 2 A m r a l A R e...

Страница 27: ...A m r a l A W R s d n o c e s 9 9 9 9 o t 0 8 5 1 e p y t 8 A m r a l A R e p y T 1 A m r a l A e e S 1 2 o t 0 9 5 1 p i r t 8 A m r a l A W R 9 9 9 9 o t 9 9 9 0 6 1 s i s e r e t s y h 8 A m r a l...

Страница 28: ...o l h t i w p u k c a b g o l a n A n o i t c e l e s l a t i g i d r e d a o l l a u n a m r o t a c i d n i e l g n i S r e d a o l l a u n a m r o t a c i d n i e l b u o D d r a w r o f d e e f h...

Страница 29: ...e H y a l e r 2 P O y a l e r 1 P O y a l e r 1 P O h t i w l o o c t a e H t u p t u o l a t i g i d 2 P O h t i w l o o c t a e H t u p t u o l a t i g i d 1 P O y a l e r 2 P O d e s U t o N h t i...

Страница 30: ...9 9 9 9 o t 9 9 9 1 1 2 t l u s e r 2 k c o l b s h t a M R 9 9 9 9 o t 9 9 9 2 1 2 t l u s e r 3 k c o l b s h t a M R 9 9 9 9 o t 9 9 9 3 1 2 t l u s e r 4 k c o l b s h t a M R 9 9 9 9 o t 9 9 9 4...

Страница 31: ...s and Field Indicators Flow Metering Magnetic Flowmeters Electromagnetic insertion type probes and watermeters Turbine Flowmeters Wedge Flow Elements Mass Flow Meters Transmitters sensors controllers...

Страница 32: ...thout notice ABB 2000 Printed in UK 06 00 ABB Instrumentation Ltd St Neots Cambs England PE19 3EU Tel 44 0 1480 475321 Fax 44 0 1480 217948 ABB Automation Inc Instrumentation Division 125 E County Lin...

Отзывы: