ELECTRICAL INSTALLATION
Fig. 2.4 OPTO22 Board Connections
2.6
Serial Connections – Figs. 2.1 to 2.4
Information.
•
Up to
10 slaves
can be connected to a single
RS422
adaptor card on a PC.
•
Up to
32 slaves
can be connected to a single
RS485
adaptor card on a PC.
The number of slaves can be increased if the driver's serial port permits.
Connections to the MODBUS serial board must be made as shown in Figs. 2.1, 2.2 or 2.4.
Connections on links with multiple slaves must be made in parallel, as shown in Fig. 2.3. When
connecting cable screens, ensure that no 'ground loops' are introduced.
The maximum serial data transmission line length for both
RS422
and
RS485
systems is 1200m. The types
of cable that can be used are determined by the total line length:
Up to 6m
– standard screened or twisted pair cable.
Up to 300m
– twin twisted pair with overall foil screen and an integral drain wire, e.g. Belden 9502
or equivalent.
Up to 1200m
– twin twisted pair with separate foil screens and integral drain wires, e.g. Belden
9729 or equivalent.