background image

8

…2

CONTROL CONFIGURATION LEVEL

2.3

Ramp/Soak Profile Program

Page Header – Profile Program.

To advance to the 

CONTROL CONFIGURATION LEVEL

 frame press the 

 switch.

Select Program
Select the program to be configured:

Ch1–1

 to 

Ch1–10

Channel 1 programs 1 to 10

Ch2–1

 to 

Ch2–10

Channel 2  programs 1 to 10 (if available)

NONE

no program selected

Program Begin
Select the program start segment, between 1 and 99.

Program End
Select the program end segment between, 1 and 99.

Select Segment
Select the segment to be programmed (1 to 99).

When all segments have been programmed, select 0 to advance to 

Repeat Program

 frame.

Segment Start Value
Set the segment start value. The segment start value can only be set if it is the first segment of
a program.

Ramp

 has different start and end set point values. A 

Soak

 has the same start and end set point

values.  Adjacent segments of different 

Ramp 

or 

Soak 

programs MUST have the same start and

end values, unless an intermediate ‘spacer’ segment is used.

Segment End Value
Set the segment end value.

If segment start/end values are the same (Soak),  advance to the 

Soak Time

 frame. If segment

start/end values are different (Ramp),  advance to 

Ramp Rate

 frame.

Soak Time
Set soak time duration required, between 0 and 999.9.

The time units (hours or minutes) are configured in 

Ramp/Soak Time Units

 frame, 

Profile Control

Page

.

Ramp Rate
Set the ramp rate.

The ramp rate is entered as the number of engineering units that change during the time period
(hours or minutes) configured in the 

Ramp/Soak Time Units 

frame, 

Profile Control Page

.

Example – if a ramp of 10

°

F at 2

°

 every minute is required, the ramp rate value entered is 2.0 (in

the minutes time base).

Ramp rates set excessively low over a wide range cannot be displayed properly at the 

Current

Profile Segment

 (

Time Remaining

) frame. This display shows a maximum of 999.9 units of time.

The display is decremental when the time remaining is less than 999.9.

Continued on next page.

Ramp/Soak

PrOFLE
PrOGrM

  NONE

Ch1–1

PG–bEG

ENd
    –.–

tIME

    ––

  –––.–

StArt

NONE

PrOGrM

Ch2–10

Channel No.

Program No.

PG–ENd

SEGMNt

SOAK

rEPEAt
––––––

RAMP

rAtE
  ––––

    ––

    ––

    ––

Содержание COMMANDER 1900 Series

Страница 1: ...User Guide Advanced Software Options COMMANDER 1900 Series Circular Chart Recorders COMMANDER 1900 100 3 198 5 dEGF OP54 5 200 5 50 8...

Страница 2: ...nditions result in degraded process system performance leading to personal injury or death Therefore comply fully with all Warning and Caution notices Information in this manual is intended only to as...

Страница 3: ...g the Engineering Flow Rate 12 4 1 2 Calculating the Count Rate High 12 4 2 Set Up Totalizer 14 Maths 5 ADVANCED CONFIGURATION LEVEL 17 5 1 Introduction to Maths 17 5 1 1 Standard Maths Block 17 5 1 2...

Страница 4: ..._ Soak Time Adjust SK AdJ ______ Run Hold Source r hSrc ______ Reset Enable rESEt ______ Skip Enable SKIP ______ SKIP b ______ Self Seeking S P SS SPt ______ Retort rEtOrt ______ Ramp Soak Profile Pro...

Страница 5: ...sary delays when a program is started see Fig 2 5 Retort function ensures safe operation under fault conditions see Fig 2 6 Power recovery function determines ramp soak profile restart position on ins...

Страница 6: ...Soak Adjust function allows the Soak time of a segment to be extended or reduced by a value preset in the Soak Adjust frame in the Ramp Soak Profile Control Page The soak time can be adjusted repeated...

Страница 7: ...e Power Down Recovery Function is only available on instruments fitted with the Timer option The Power Recovery function allows pre selection of the restart position within a ramp soak profile when po...

Страница 8: ...ctivate program run hold The run hold source is level triggered i e the active logic state must be maintained to select the alternative function If a program is activated or placed into operator hold...

Страница 9: ...he Profile States Page OPERATOR LEVEL Skip Enable Select ENBL Y to enable or ENBL N to disable the Skip Segment frames in the Profile States Page OPERATOR LEVEL Self Seeking Set Point If ON is selecte...

Страница 10: ...ss an intermediate spacer segment is used Segment End Value Set the segment end value If segment start end values are the same Soak advance to the Soak Time frame If segment start end values are diffe...

Страница 11: ...The value set applies above and below the Process Variable Setting 0 turns off the holdback hysteresis function A guaranteed ramp or soak is a segment whose time is counted only if the process variabl...

Страница 12: ...total 1 Total 1 external counter drive Wrap around and count only available if totalizer option fitted MAN x AUtO x Control mode selected for controller 1 or 2 Manual control Automatic control 2Nd x...

Страница 13: ...Rate D P dEC Pt ____ Count Rate Low CNt LO ____ CUtOFF ____ PrESEt tOtL _ Reset Controls Stop Go Controls rESEt ______ rSt SrC ______ Reset Source StOPGO ______ Stop Go Source SG SrC ______ Set Up Cl...

Страница 14: ...their own power supplies can be driven using 4 relay and digital output module options 4 1 1 Converting the Engineering Flow Rate Example A and B To calculate the count rate high the engineering flow...

Страница 15: ...2500 0 Preset Value Predetermine d Value Preset Predetermine d Count Count Up 9999 0000 0000 Count Rate High Low CNt HI 06 94 CNt LO 0000 Count Direction Preset Value Predetermine d Value Count Up Wra...

Страница 16: ...e right Secure Reset The Secure Total may be reset to either 00000000 or 99999999 depending on the count direction if required Select YES to reset the counter or NO to retain the current counter value...

Страница 17: ...termined Value CNtdIr dN decremental counter Preset Value Predetermined Value Predetermined Value If the wrap around facility is used see below the front panel total is automatically reset to the Pres...

Страница 18: ...itted when the Predetermined Value is reached Reset Enable Select ENBL Y to enable or ENAbL N to disable the counter reset frame in the Totals Page OPERATOR LEVEL Reset Source Select the digital sourc...

Страница 19: ...end The example below shows the construction of a maths block for the following equation 5 ADVANCED CONFIGURATION LEVEL Maths Element 1 Constant 8 Constant 1 Maths Block 4 Maths Block 1 Input 6 Input...

Страница 20: ...essure input source T Temperature temperature input source Tr Reference temperature for the scaling constant used Pr Reference pressure for the scaling constant used The temperature units used by the...

Страница 21: ...sition F B 1 Remote S P 1 Local S P 1 Process Variable 1 Input A Input t Constant 8 Constant 1 Maths Block 4 Maths Block 1 Input 6 Input 1 Channel 1 2 Output Channel 1 2 Output cool Channel 1 2 Output...

Страница 22: ...ition F B 1 Remote S P 1 Local S P 1 Process Variable 1 None Input a Input t Constant 8 Constant 1 Maths Block 4 Maths Block 1 Input 6 Input 1 Channel 1 2 Output Channel 1 2 Output cool Channel 1 2 Ou...

Страница 23: ...erage reset signal 5 1 5 Real Time Average The real time average function averages a continually varying input over a set time scale between 1 and 1440 minutes 24 hours Any process variable remote set...

Страница 24: ...ock Function Select the maths block function required AVErGE Averages a continually varying input over a set period of time LO VAL Holds minimum value measured on input variable HI VAL Holds maximum v...

Страница 25: ...nt 4 operator 2 Select the operator required for element 4 For description of operators refer to Maths Block n Element 2 frame Maths Block n Element 5 operand 3 Select the source required for element...

Страница 26: ...Return to Select Maths Function frame Maths High low Input Select the variable source whose minimum or maximum value is to be detected For a description of input output sources refer to Table 5 1 on p...

Страница 27: ...e Temperature Decimal Point Set the number of decimal places required for the reference temperature 0 to 3 places Pressure Input Select the process variable source required for the pressure input Pres...

Страница 28: ...3 Process variable 4 Process variable 3 PFb 1 rSP 1 2 SP 1 LSP 1 SP 1 PV 1 NONE No source required Position Feedback 1 Remote set point 1 Local set point 1 Set point 1 Process variable 1 Heat cool on...

Страница 29: ...et point If the maths result is to be assigned to a process variable or remote set point it is necessary to set up fault detection levels broken sensor actions and an engineering range high low in the...

Страница 30: ...on specific days hours or minutes for an exact period of time Timer ON OFF states can be used to energize relay outputs acknowledge alarms stop the chart select auto manual control modes and local rem...

Страница 31: ...isabled on hour set to All on minute set to 20 minutes duration in hours set to 0 hours duration in minutes set to 40 minutes Relay On Monday 00 20am Relay Off 01 00am 01 20am 02 00am 02 20am 03 00am...

Страница 32: ...Select ON to enable or OFF to disable Tuesday Enable Repeat as above for Tuesday to Sunday On Hour Set the hour at which the timer becomes active If ALL is selected the timer becomes active every hour...

Страница 33: ...day and time are correct in the above frames select NO to return to the Set Up Clock frame To set the clock s date day or time select YES Year Set the year Month Set the month Date Set the date Day S...

Страница 34: ...32 NOTES...

Страница 35: ...ion pH conductivity and dissolved oxygen transmitters and sensors ammonia nitrate phosphate silica sodium chloride fluoride dissolved oxygen and hydrazine analyzers Zirconia oxygen analyzers katharome...

Страница 36: ...notice ABB 2001 Printed in UK 02 01 ABB Automation Ltd Howard Road St Neots Cambridgeshire PE19 8EU UK Tel 44 0 1480 475 321 Fax 44 0 1480 217 948 ABB Automation Inc 125 E County Line Road Warminster...

Отзывы: