21
TRANSFORMER COMPONENTS
—
Appendix A: MODBUS communication
A1
MODBUS register
Register address
Operation
Notes
Operation for monitoring
0x2000
R
Level value (0-100%)
0x2001
R
Minutes from the last powering
0x2002
R
Days from the last powering
0x2003
R
Max level value (%) in the current day
0x2004
R
Min level value (%) in the current day
0x2005
R
Number of powering lost in the day
0x2006
R
Minimum range value
0x2007
R
Maximum range value
0x200A
R
Software version
Data logging**
0x2100
R
Max level in the day -1
0x2101
R
Min level in the day -1
0x2102
R
Max level in the day -2
0x2103
R
Min level in the day -2
0x2104
R
Max level in the day -3
0x2105
R
Min level in the day -3
…
…
…
0x215C
R
Max level in the day -23
0x215D
R
Min level in the day -23
0x215E
R
Max level in the day -24
0x215F
R
Min level in the day -24
Events log
0x2300
R
Events number
0x2301
R
Timestamp Hi [Event 1]*
0x2302
R
Timestamp Low [Event 1]*
0x2303
R
Event type: value 4=Change Date[Event 1]
0x2304
R
Level Value at the moment of the event [Event 1]
…
…
…
0x248D
R
Timestamp Hi [Event 100]*
0x248E
R
Timestamp Low [Event 100]*
0x248F
R
Event type: value 4=Change Date[Event 100]
0x2490
R
Level Value at the moment of the event [Event 100]
Table 7
*Date and time of an event are calculated in this way:
Event Date/Time = Timestamp Hi (seconds) + (216) x Timestamp Low (seconds) + (01-Jan-2014 00hh:00min:00sec)
** The daily maximum and minimum data were saved starting from the nearest day, in registers 0x2100 and 0x2101, at the farthest day, in registers
0x215E e0x215F.
Содержание Comem OLI
Страница 3: ...3 TRANSFORMER COMPONENTS 2 Drawings 2 1 Comem OLI Figure 2 Figure 1 2 2 Comem eOLI ...
Страница 7: ...7 TRANSFORMER COMPONENTS 2 Drawings 2 5 Comem L220 2 5 1 Radial 2 5 1 Axial Figure 9 Figure 10 ...
Страница 9: ...9 TRANSFORMER COMPONENTS 2 7 Comem eViewer Figure 13 ...
Страница 19: ...19 TRANSFORMER COMPONENTS Figure 25 5 Electrical connection ...
Страница 23: ...23 TRANSFORMER COMPONENTS ...