Signals
5.10.
Table 5.10-1 SSCBR input signals
Description
Default
Type
Name
Phase A Current
0
DOUBLE
R_IL1
Phase B Current
0
DOUBLE
R_IL2
Phase C Current
0
DOUBLE
R_IL3
Signal for open posi-
tion of apparatus from
I/O
0
INT
CB_POS
Gas Pressure
0
BOOLEAN
R_GAS_PRES
Spring charge
0
BOOLEAN
R_SPRING_CHARG
Inactive days
0
INT
R_INACT_DAYS
Number of CB opera-
tion
0
INT
R_NUM_CB_OPR
Table 5.10-2 SSCBR Output Signals
Description
Default
Type
Name
CB open travel time
exceeded set value
0
BOOLEAN
TrvTOpAlm
CB close travel time
exceeded set value
0
BOOLEAN
TrvClAlm
Number of CB opera-
tions exceeds alarm
limit
0
BOOLEAN
CbOprAlm
Remaining life of CB
exceeded alarm limit
0
BOOLEAN
CBLifeAlarm
Inactive days
exceeded set value
0
BOOLEAN
InActAlm
Accumulated currents
power (I
y
t),exceeded
alarm limit
0
BOOLEAN
CBAccEneAlarm
Spring charging time
has crossed the set
value
0
BOOLEAN
SprChrAlm
Pressure below alarm
level
0
BOOLEAN
PresAlam
CB Open travel time
0 = false
DOUBLE
TrvOpnTm
CB Close travel time
0 = false
DOUBLE
TrvClTm
Phase A accumulated
energy
0 = false
DOUBLE
CBAccEnePhsA
55
COM600 series 5.1
1MRS758734
Substation Analytics Technical Manual