Grid Automation Controller COM600 4.0

FDIR Operation Manual

Содержание COM600 4.0

Страница 1: ...Grid Automation Controller COM600 4 0 FDIR Operation Manual ...

Страница 2: ......

Страница 3: ...tection setting groups 12 3 3 FDIR simulation 12 3 3 1 Simulating faults 12 3 3 2 Simulating load 13 3 4 Changing source capacity limit 14 3 5 Viewing the active settings group 15 3 6 Viewing FDIR log 15 3 7 FDIR testing 16 3 7 1 Testing FDIR logic 16 3 7 2 Setting IEDs to simulation mode 17 3 7 3 Simulating fault in Manual mode 17 3 7 4 Simulating return to normal 22 3 7 5 Simulating FDIR blockin...

Страница 4: ...4 ...

Страница 5: ...disclosed only in accordance with the terms of such license Copyright 2012 ABB All rights reserved Trademarks 1 2 ABB is a registered trademark of ABB Group All other brand or product names men tioned in this document may be trademarks or registered trademarks of their respective holders General 1 3 This manual provides information on the FDIR functionality of COM600 Human Machine Interface HMI In...

Страница 6: ...sked to enter the string MIF349 in a field The string is shown as follows in the procedure MIF349 Variables are shown using lowercase letters sequence name Use of symbols 1 5 This publication includes warning caution and information icons that point out safety related conditions or other important information It also includes tip icons to point out useful information to the reader The correspondin...

Страница 7: ...cal IEC 61850 device that behaves as its own commu nication node in the IEC 61850 protocol Intelligent Electronic Device Series of standards specifications aiming at open connectivity in industrial automation and the enterprise systems that support industry OPC Named data item Property Abbreviations 1 7 The following is a list of abbreviations associated with COM600 that you should be familiar wit...

Страница 8: ...History Product revision Document version date Document revised 4 0 B 31 5 2012 8 1MRS757279 Grid Automation Controller COM600 4 0 FDIR Operation Manual ...

Страница 9: ...IR updates the network status by receiving switch status and load signals from the IED When a fault happens in the network FDIR on COM600 detects the location of the fault and issues switch operation commands from the algorithm to isolate faulted feeder sections from the network and restore the service to the healthy section It also sends commands to IEDs controlling switches to return to the norm...

Страница 10: ...to enable disable FDIR and setup parameters simulate faults and view FDIR logs You can open the FDIR Control dialog in the COM600 HMI by selecting FDIR in the menu bar FDIR_control_dialog png Figure 3 1 1 FDIR Control dialog 10 1MRS757279 Grid Automation Controller COM600 4 0 FDIR Operation Manual ...

Страница 11: ...y out the same procedures manually In the Test mode you can select any switch to simulate a fault FDIR produces isolation and restoration commands without sending the actual commands to the device To change the FDIR running mode 1 In COM600 HMI select FDIR 2 In the FDIR Control dialog select the FDIR Mode tab 3 In the FDIR Mode list select Auto Manual or Test Enabling or disabling logging 3 2 3 To...

Страница 12: ...DIR operation If the Setting Group function is enabled the system will check the load change on the switch before the FDIR operation The system will send a change setting group command to the IED controlling the switch if necessary To enable or disable changing of protection setting groups 1 In COM600 HMI select FDIR 2 In the FDIR Control dialog select the FDIR Mode tab 3 In the Group Setting list...

Страница 13: ...st select the switch name 5 Click Simulate Lockout If the Simulate Lockout button is not enabled the switch is not in the simulation mode Simulating load 3 3 2 The node load can be changed to run a different simulation scheme if the IED is in the simulation mode 13 Grid Automation Controller COM600 4 0 1MRS757279 FDIR Operation Manual ...

Страница 14: ...ts field type a new load value 5 Click Set Measurement Changing source capacity limit 3 4 To change source capacity limit 1 In COM600 HMI select FDIR The FDIR Control dialog opens 2 In the FDIR Control dialog select the Source Capacity tab FDIR_Simulate_Fault Figure 3 4 1 Fault simulation 3 In the Source ID list select the source name 14 1MRS757279 Grid Automation Controller COM600 4 0 FDIR Operat...

Страница 15: ...settings group 3 5 To view the active settings group for a switch 1 In COM600 HMI select FDIR 2 In the FDIR Control dialog select the Settings Group tab 3 Select the switch from the Switch ID list You can see the active settings group below the list Viewing FDIR log 3 6 To view the FDIR log 1 In COM600 HMI select FDIR 2 In the FDIR Control dialog select the Logs tab You can see time and events on ...

Страница 16: ... feature to verify the FDIR logic You can test the functions as instructed in the following sections 3 7 2 Setting IEDs to simulation mode 3 7 3 Simulating fault in Manual mode 3 7 4 Simulating return to normal 3 7 5 Simulating FDIR blocking 16 1MRS757279 Grid Automation Controller COM600 4 0 FDIR Operation Manual ...

Страница 17: ...e are IEDs in live mode the fault simulation can cause operation on the live IEDs 3 In Gateway Management tool select Reset and click Update Reload Simulating fault in Manual mode 3 7 3 This section shows the simulation of the fault on load L30201 First in FDIR Control dialog set FDIR mode to Manual see Figure 3 7 3 1 17 Grid Automation Controller COM600 4 0 1MRS757279 FDIR Operation Manual ...

Страница 18: ...Set_FDIR_Manual_Mode PNG Figure 3 7 3 1 Setting FDIR mode to Manual 18 1MRS757279 Grid Automation Controller COM600 4 0 FDIR Operation Manual ...

Страница 19: ...ch status and proper measurements in COM600 HMI to make sure the radial network is valid and select the path for testing To simulate a fault 1 In COM600 HMI select FDIR 2 In the FDIR control dialog select the FDIR Simulation tab 3 Select B30201 in the Switch ID list and click Simulate Lockout In the single line diagram the swith B30201 opens and the alert icon flashes in the header area 4 Click th...

Страница 20: ...3 7 3 3 Fault detected 5 In the FDIR Mode tab click Execute Isolation if the suggestion is valid or Ignore In COM600 HMI the isolation switch must be open 20 1MRS757279 Grid Automation Controller COM600 4 0 FDIR Operation Manual ...

Страница 21: ...u have clicked Execute Isolation Fault_isolated PNG Figure 3 7 3 4 Fault isolated 6 In the FDIR Mode tab run the load restoration by clicking Excecute Restoration if the suggestion is valid or click Ignore 21 Grid Automation Controller COM600 4 0 1MRS757279 FDIR Operation Manual ...

Страница 22: ...tem will try to return to pre fault normal mode To simulate returning to normal 1 In the FDIR Control dialog select the switch B30201 and click Clear Lockout 2 In COM600 HMI click the switch B30201 and close it by clicking Close and then Operate in the Switch device control dialog You can see the alert icon flashing in the header area 3 Click the alert icon 4 In the FDIR Mode tab of the FDIR Contr...

Страница 23: ...al state Simulating FDIR blocking 3 7 5 FDIR is blocked if the communication to the IED is bad the switch is hot line tagged or the IED is in the fault mode the Health attribute is showing warning or alarm You can test this blocking feature also in simulation mode 23 Grid Automation Controller COM600 4 0 1MRS757279 FDIR Operation Manual ...

Страница 24: ...fault mode R20202 will trip and R20103 and R20203 can be opened to isolate the fault After the isolation the loads 20102 and L20203 have two possible load restoration paths to close R20102 and R20204 In the following testing example you can simulate a Hot Line Tag on the path from R20204 24 1MRS757279 Grid Automation Controller COM600 4 0 FDIR Operation Manual ...

Страница 25: ...nd apply Hot Line Tag on it FDIR_Hot_Line_Tag png Figure 3 7 5 2 Applying Hot Line Tag 2 Select FDIR FDIR Control 3 Select Switch ID R20202 and click Simulate Lockout to simulate fault 25 Grid Automation Controller COM600 4 0 1MRS757279 FDIR Operation Manual ...

Страница 26: ...ab of the FDIR Control dialog click Execute Isolation 5 Restore load using a new path by clicking Execute Restoration Load_restored_from_one_path_only png Figure 3 7 5 4 Load restored from only one path 26 1MRS757279 Grid Automation Controller COM600 4 0 FDIR Operation Manual ...

Страница 27: ...n the switch before the FDIR operation If necessary it sends a change setting group command to the switch For more information on how to enable disable changing of protection settings group see 3 2 1 Enabling or disabling FDIR The function is demonstrated with a scheme in Figure 3 7 6 1 protection_settings_group_scheme Figure 3 7 6 1 Scheme for changing protection settings group 27 Grid Automation...

Страница 28: ... is closed the load exceeds the threshold setting for the current group see Figure 3 7 6 2 For more information on configuring the protection settings group see FDIR Configuration Manual Threshold_Setting_Group1 png Figure 3 7 6 2 Setting Group 1 Threshold is set at 289 28 1MRS757279 Grid Automation Controller COM600 4 0 FDIR Operation Manual ...

Страница 29: ...rotection settings group 2 Use FDIR Configuration Tool to configure the protection settings group for the switch IED3 3 Simulate the fault at the switch IED1 4 Isolate IED2 as recommended by FDIR 5 FDIR detects that protection settings group needs to be changed and recommends changing from Group 1 to Group 2 Click the Change Setting Group button or the Setting Group tab to view the pro tection set...

Страница 30: ...p png Figure 3 7 7 1 1 Changing protection settings group detected 6 On the Settings Group tab click Set below the desired group to change the group 30 1MRS757279 Grid Automation Controller COM600 4 0 FDIR Operation Manual ...

Страница 31: ... 2 When FDIR is in Auto mode and changing protection settings group is enabled the system checks the load change on the switch and attempts to send a command to change the setting group on the switch based on the configured threshold setting Changing protection settings group can be demonstrated using the same example scheme as in Figure 3 7 6 1 31 Grid Automation Controller COM600 4 0 1MRS757279 ...

Страница 32: ...32 ...

Страница 33: ......

Страница 34: ...ghts reserved ABB Oy Distribution Automation P O Box 699 FI 65101 VAASA FINLAND Tel 358 10 22 11 Fax 358 10 224 1094 ABB Inc Distribution Automation 655 Century Point Lake Mary FL 32746 USA Tel 1 407 732 2000 Fax 1 407 732 2335 www abb com substationautomation ...