Key
Display
Parameter
Parameter values
underlined or FS = Factory Setting
change
defines integral (reset) time. This action component
prevents stationary control deviations.
Notice
Changing this parameter has decisive effects on the
control action. A big integral action time in a slow
control, whereas a too small value can lead to over-
shooting and even to a destabilisation of the entire
control process.
0...120...3600 s
,
defines the derivative (rate) time for the differential
component. This component enables quicker reaction
to changes in the stationary status.
Notice
A modification of this parameter has decisive effects
on the control action. A too small derivative time ini-
tially produces drastic overhooting, whereas a too big
value produces oscillations and even destabilisation
of the entire control process.
0...30...1000 s
,
PV
back to the main operator level
or to 1. menu level
for at
least 6 s
determines if the keys are disabled for making
modifications on parameter values
Notice
The keyboard is disabled with immediate effect!
0
activated
1
deactivated
,
defines the parameters which can be directly
accessed on the main operator level
0
no parameter
1
2
3
4
,
5
,
6
,
7
,
,
,
defines proportional cycle time for relay output 1
Example
Cycle time duration 10 s and calculated output signal
40 %:
Output relay closes for 4 s and opens afterwards for
6 s
0...120 s
FS relay: 20 s
analog: 0 s
,
Parameter definition
9