6
CE M11- FB P. X X X E A RTH LE A K AG E MON ITOR
M A N UA L
—
CEM11-FBP.120
Rotary switch set to
Earth fault current threshold [mA]
Comment
0
240
Tolerance ± 30 %
1
2000
Tolerance ± 10 %
2
4000
Tolerance ± 10 %
3
5600
Tolerance ± 10 %
4
8000
Tolerance ± 10 %
5
9600
Tolerance ± 10 %
6
12000
Tolerance ± 10 %
7
13600
Tolerance ± 10 %
8
for functional test
9
for functional test
—
CEM11-FBP.60
Rotary switch set to
Earth fault current threshold [mA]
Comment
0
120
Tolerance ± 30 %
1
1000
Tolerance ± 10 %
2
2000
Tolerance ± 10 %
3
2800
Tolerance ± 10 %
4
4000
Tolerance ± 10 %
5
4800
Tolerance ± 10 %
6
6000
Tolerance ± 10 %
7
6800
Tolerance ± 10 %
8
for functional test
9
for functional test