CE M11- FB P. X X X E A RTH LE A K AG E MON ITOR
M A N UA L
The following tables show the current thresholds for each device variant.
—
CEM11-FBP.35
Rotary switch set to
Earth fault current threshold [mA]
Comment
0
100
Tolerance ± 30 %
1
500
Tolerance ± 10 %
2
1000
Tolerance ± 10 %
3
1400
Tolerance ± 10 %
4
2000
Tolerance ± 10 %
5
2400
Tolerance ± 10 %
6
3000
Tolerance ± 10 %
7
3400
Tolerance ± 10 %
8
for functional test
9
for functional test
—
CEM11-FBP.20
Rotary switch set to
Earth fault current threshold [mA]
Comment
0
80
Tolerance ± 30 %
1
300
Tolerance ± 10 %
2
550
Tolerance ± 10 %
3
750
Tolerance ± 10 %
4
1000
Tolerance ± 10 %
5
1300
Tolerance ± 10 %
6
1500
Tolerance ± 10 %
7
1700
Tolerance ± 10 %
8
for functional test
9
for functional test
—
Product description
Setting the earth fault current
The current threshold when the CEM11 signals an earth fault can be adjusted with a rotary switch.
The test position can be used to test the CEM11 and connected devices like the UMC100.3. This allows simple
verification if the earth fault related settings in the UMC100.3 are all done correctly and e.g. lead to a trip.