ABB CA-26 Скачать руководство пользователя страница 6

41-337.31B

6

(Viewed from top of switch between cover and frame).
This can be done by loosening the mounting screw in
the molded pedestal and moving the ICS in the down-
ward position.

a.

Contact Wipe – Adjust the stationary contact so
that both stationary contacts make with the moving
contacts simultaneously and wipe 1/64” to 3/64”
when the armature is against the core.

b.

Target – Manually raise the moving contacts and
check to see that the target drops at the same
time as the contacts make or 1/16” ahead. The
cover may be removed and the tab holding the
target reformed slightly if necessary. However,
care should be exercised so that the target will
not drop with a slight jar.

If the pickup is low, the front cover must be removed
and the leaf springs on each side bent outward
equally.

7.6.

Sensitive Fault Detector

Loosen the lock nut at the top of the element and run
the core screw down until it is flush with the top of the
lock nut. Back off the Micarta disc by loosening the
two lock nuts. Apply 0.15 amperes to terminals 14
and 15. Operate the moving element by hand and
allow the current to hold the moving contact disc
against the stationary contacts. Now, screw up the

core screw slowly. This causes the plunger to move
up, compressing the spring until a point of maximum
deflection is reached. Further upward motion will
cause the plunger to drop part way out of the coil,
thus diminishing the spring pressure on the contacts.
By thus adjusting the core screw up or down the
maximum spring deflection for this value of current
may be found.

Then lock the core screw in place. Next, adjust the
de-energized position of the plunger by raising the
Micarta disc until the plunger just picks up electrically
at the 0.15 ampere value.

7.7.

Electrical Checkpoints

Figures 9 and 10 will aid in trouble shooting the
CA-16. These curves show the operating current to
trip the relay for different restraint current for one
restraint element as well as for six restraint elements
connected in series.

8.0

RENEWAL PARTS

Repair work can be done most satisfactorily at the
factory. However, interchangeable parts can be fur-
nished to customers who are equipped for doing
repair work. When ordering parts, always give the
complete nameplate data.

Courtesy of NationalSwitchgear.com

Содержание CA-26

Страница 1: ...fety classification of the electric equipment and systems in nuclear power generating stations that are essential to emergency shutdown of the reactor containment isolation cooling of the reac tor and heat removal from the containment and reac tor or otherwise are essential in preventing significant release of radioactive material to the environment The current transformers should not saturate whe...

Страница 2: ...41 337 31B 2 Figure 1 CA 16 Front View Figure 2 CA 16 Rear View Courtesy of NationalSwitchgear com ...

Страница 3: ...de rod by two small nuts Its position determines the pick up current of the element The auto transformer is designed to saturate at high values of current to limit the amount of current to the contactor switch 2 3 1 Indicating Contactor Switch Unit ICS The dc indicating contactor switch is a small clapper type device A magnetic armature to which leaf spring mounted contacts are attached is attract...

Страница 4: ... CA 16 To determine the ac connections identify each pri mary circuit as either a source or feeder As defined here a feeder contributes only a small por tion of the total fault current contribution for a bus fault Otherwise the circuit is a source Next lump a number of feeders into a feeder group by paralleling feeder ct s taking the precaution that each feeder group has less than 14 amperes load ...

Страница 5: ...eres 6 2 Routine Maintenance All contacts should be periodically cleaned A contact burnisher is recommended for this purpose S 182A836H01 The use of abrasive material for cleaning contacts is not recommended because of the danger of embedding small particles in the face of the soft silver and thus impairing the contact 7 0 CALIBRATION Use the following procedure for calibrating the relay if the re...

Страница 6: ...d 15 Operate the moving element by hand and allow the current to hold the moving contact disc against the stationary contacts Now screw up the core screw slowly This causes the plunger to move up compressing the spring until a point of maximum deflection is reached Further upward motion will cause the plunger to drop part way out of the coil thus diminishing the spring pressure on the contacts By ...

Страница 7: ...41 337 31B 7 This Page Reserved for Notes Courtesy of NationalSwitchgear com ...

Страница 8: ...41 337 31B 8 Figure 3 Internal Schematic of the Type CA 16 Bus Relay Sub 1 3532A95 Courtesy of NationalSwitchgear com ...

Страница 9: ...41 337 31B 9 Figure 4 Typical Time Curves of the CA 16 Differential Relay Sub 1 537956 Courtesy of NationalSwitchgear com ...

Страница 10: ...41 337 31B 10 Figure 5 Typical Burden Characteristics of the Types CA 16 and CA 26 Relays Curve 537957 Courtesy of NationalSwitchgear com ...

Страница 11: ...41 337 31B 11 Figure 6 External Schematic of One Set of Type CA 16 Relays for the Protection of a Three and Four Circuit Bus Sub 5 187A424 Courtesy of NationalSwitchgear com ...

Страница 12: ...41 337 31B 12 Figure 7 External Schematic of the Type CA 16 Relays for Protection of Six Circuit Bus with Three Feeder Groups Sub 5 187A425 Courtesy of NationalSwitchgear com ...

Страница 13: ...41 337 31B 13 Figure 8 Diagram of Test Connections for the CA 16 Relay Sub 4 187A426 Courtesy of NationalSwitchgear com ...

Страница 14: ...41 337 31B 14 Figure 9 Percentage Slope Curve of the CA 16 Relay with One Restraint Winding Sub 1 849A450 Courtesy of NationalSwitchgear com ...

Страница 15: ...41 337 31B 15 Figure 10 Percentage Slope Curve of the CA 16 Relay with Six Restraint Windings in Series Sub 2 849A343 Courtesy of NationalSwitchgear com ...

Страница 16: ...oral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 visit our website at www abbus com papd 41 337 31B Figure 11 Outline and Drilling for the CA 16 Relay in FT 32 Case Sub 1 3519A69 Courtesy of NationalSwitchgear com ...

Отзывы: