C1300
Advanced circular chart recorder
3 Configuration
28
IM/C1300 Rev. J
Engineering Range High
Set the maximum engineering value required, within the limits shown in Table 3.2.
Engineering Range Low
Set the minimum engineering value required, within the limits shown in Table 3.2.
Chart Range High
Set the maximum value, in engineering units, required on the chart.
Note.
If the
Engineering Range High
setting is changed, the
Chart Range High
setting is reset
automatically to the same value.
Chart Range Low
Set the minimum value, in engineering units, required on the chart.
Note.
If the
Engineering Range Low
setting is changed, the
Chart Range Low
setting is reset
automatically to the same value.
Continued on next page.
Degrees Celsius
Degrees Fahrenheit
Linearizer Type
Minimum
Maximum
Minimum Span
Minimum
Maximum
Minimum Span
Type K
–100
1300
65
–148
2372
117
Types R & S
–18
1700
320
0
3092
576
Type T
–250
300
60
–418
572
108
Type J
–100
900
50
–148
1652
90
Type E
–100
900
45
–148
1652
81
Type N
–200
1300
90
–328
2372
162
Type B
–18
1800
710
0
3272
1278
Rtd
–200
600
25
–328
1112
45
Performance accuracy is not guaranteed below 400°C (725°F) for types B, R and S thermocouples.
Minimum span below zero for Type T thermocouples is 70°C (126°F).
Minimum span below zero for Type N thermocouples is 105°C (189°F).
THC standard DIN 4730 IEC 584.
RTD standard DIN 43760 IEC 751.
Engineering Range High and Low
Linearizer Type
Minimum
Maximum
Square Root
–999
9999
3/2
5/2
None
Table 3.2 Limits of Engineering Ranges
Pen 1 Eng. Hi
010.00 mV
Pen 1 Eng. Lo
000.00 mV
Pen 1 Chart Hi
010.00 mV
Pen 1 Brk Sensor
Downscale
Pen 1 Chart Lo
000.00 mV