Pos: 60 /#Neustr uktur#/Online-Dokumentati on (+KN X)/Bedi enung/Ti mer/Partyfunktion - 6411 @ 30\mod_1348754487880_15.docx @ 240033 @ 3 @ 1
7.2.6
Party function
The Party function can be activated only when combining the flush-mounted inserts 6411 U/...-101 and control
elements 6430-... With this function the flush-mounted insert is excluded from a group control. This means that
signals which arrive via the extension unit inputs and local operation are ignored.
The function can only be activated when the blind is in the top end position. Please observe the relay operating
time of 3 minutes.
Enable
•
Activate the UP button for 5 seconds.
As acknowledgement, the blind travels down for two seconds and then back up to the top end position.
Deactivate
•
Actuate the DOWN button for 5 seconds.
As acknowledgment, the blind moves down. The deactivation is carried out automatically after approximately
8 hours.
Activating the party function deactivates the sun protection, the twilight and the awning function. The Party
function cannot be activated in "Central unit" and "Programming" operating modes.
Pos: 61 /#Neustr uktur#/Online-Dokumentati on (+KN X)/Überschriften (--> Für all e D okumente <--)/2. Ebene/S - T /Stör ungsbeseitigung @ 21\mod_1330945986708_15.docx @ 201048 @ 3333333 @ 1
7.3
Fault rectification
Pos: 62 /#Neustruktur#/Online-Dokumentation (+KNX)/Störungsbeseitigung/Timer/Störungsbeseitigung - 6411 @ 31\mod_1349182561196_15.docx @ 241392 @ 333333 @ 1
Diagnosis
Possible cause
Fault rectification
Blinds move differently (with group control)
Outputs have been switched
Switch outputs on 6411 U/S-101
Extension units have been switched
Switch extension unit inputs on 6411 U/S-
101
Load and control lines have been installed
too close
Separate load lines and control lines
Adhere to a minimum distance of 5 cm
Blind does not move during group control
Extension unit input with higher highest
priority is active (e.g. wind alarm)
–
Blind does not move
Thermal protection of motor is active
Wait for a short period
Slats are not adjustable
Incorrect operating mode is set
Check operating mode
Blind no longer travels via extension unit
and local control
Party function is active
Deactivate party function