2-1

MN704

Chapter 2

Installation

WARNING:  Do not use this drive in an explosive environment. An explosion can cause serious or fatal injury.  

This drive is not explosion proof.

MOUNTING INSTRUCTIONS

It is recommended that the control be mounted on a flat surface with adequate ventilation. Leave 

enough room to allow for AC line, motor connection, and other wiring that is required. Care should 

be taken to avoid extreme hazardous locations where physical damage can occur. When mounting 

the control in an enclosure, the enclosure should be large enough to allow for proper heat dissipation 

so that the ambient temperature does not exceed 40°C (104°F). If the optional Auxiliary Heat Sink 

is used, mount the control in such a manner that there is unrestricted air flow through the heat sink 

cooling fins.  See Figure 2-1.

Figure 2-1  Mechanical Specifications (Inches/mm)

CONTROL

M

O

UN

T

IN

G

"D

"

2

S

L

O

T

S

POTENTIOMETER

(SUPPLIED)

MAIN SPEED

OPTIONAL AUXILIARY HEAT SINK

.95

24.1

1.25

31.8

.50

12.7

.98

24.9

5.63

143

3.11

(79.0)

5.63

142.9

6.25

159

1.25
31.8

1.38
34.9

7.00

178

1

ANTI-

ROTATION

PIN

3/8-32
BUSHING

3/8"

SHAFT

1/4" ROUND

1/2"

P

2

P

3

P

.44

11.1

.13

3.1

MOUNTING "B"
TAPPED 10-32
(3 PLACES)

FUSE HOLDER & FINGER-SAFE
COVER MOUNTING HOLES
TAPPED 6-32
(2 PLACES)

MOUNTING "A"

6 SLOTS

3.64

92.5

3.10

78.5

.22

5.6

4.30

109

2.15

54.6

.25

6.4

.18

4.6

.64

16.3

1.75

44.5

1.75

44.5

.75

19.1

1.50

38.1

3.00

76.2

Electrical Connections

Important Application Note: To avoid erratic operation, do not bundle the AC line and motor wires with
signal or control wiring. Also, do not bundle motor wires from multiple controls in the same conduit. 

Use shielded cables on all signal wiring over 12 (30 cm). The shield should be earth grounded on the 

control side only. Wire the control in accordance with the National Electrical Code requirements and 

other local codes that may apply.

Table 2-2 Minimum Supply Wire Size Requirements

Max Motor 

Current (ADC)

90 - 130 VDC 

Motors  

(Max HP)

180 Volt DC 

Motors (Max 

HP)

Min Wire Size (Cu)

Maximum 50 Ft.

Maximum 100 Ft.

AWG

mm

2

AWG

mm

2

6

0.5

1

16

1.3

14

2.1

12

1

2

14

2.1

12*

3.3*

16

1.5

3

12*

3.3*

12*

3.3*

AC Line Fusing

A 25 Amp AC line fuse is factory installed in the AC line fuse holder. It is recommended that a 12 Amp AC line 

fuse be installed for motors rated 7.5 Amps DC or less. Fuses should be normal blow ceramic 3AG, MDA, 

or equivalent. For USA 230 Volt AC lines, separate branch circuit protection for each line must be used. The 

optional Barrier Terminal Board (Catalog No. BC147) contains prewired AC line and armature fuse holders.

Содержание Baldor BC141

Страница 1: ...5 17 Installation Operating Manual MN704 BC141 BC142 BC142 5 BC142 6 DC Control ...

Страница 2: ...Any trademarks used in this manual are the property of their respective owners Important Be sure to check www baldor com to download the latest version of this manual in Adobe Acrobat PDF format ...

Страница 3: ...d Connection Shunt Wound Motors Only 2 3 Full Voltage Field 2 3 Plug In Horsepower Resistor Armature Fuse Kit 2 3 Armature Fuse 2 3 Remote Main Speed Potentiometer Connection 2 4 Voltage Following Connection 2 4 Enable Circuit Connection 2 5 Inhibit Circuit Connection 2 6 DC Tachometer Connection 2 6 Armature Switching and Dynamic Braking 2 8 Startup Adjustments 2 8 Trimpot Adjustments 2 9 Operati...

Страница 4: ...ith a factory installed 25 Amp AC line fuse a 5 kΩ Main Speed Potentiometer and QD terminals All models are UL Listed USA and Canada and CE Approved SAFETY NOTICE A Warning statement indicates a potentially hazardous situation which if not avoided could result in injury or death A Caution statement indicates a potentially hazardous situation which if not avoided could result in damage to property ...

Страница 5: ...ielectric Withstand test on the motor Failure to disconnect motor from the control will result in extensive damage to the control The control is tested at the factory for high voltage leakage resistance as part of Underwriter Laboratory requirements Caution Do not connect AC power to the Motor terminals A1 and A2 Connecting AC power to these terminals may damage the control Caution Baldor recommen...

Страница 6: ...6 3 2 3 100 200 0 90 12 8 75 6 24 16 1 5 1 1 100 Table 1 2 General Performance Specifications Description Specification Factory Setting Speed Range Ratio 50 1 Armature Feedback Load Regulation 0 Full Load 50 1 Speed Range Base Speed 1 Tachometer Feedback Load Regulation 0 Full Load 50 1 Speed Range Set Speed 1 Line Voltage Regulation at Full Load 10 Line Variation Speed 0 5 Control Linearity Speed...

Страница 7: ...1 4 MN704 ...

Страница 8: ...PED 10 32 3 PLACES FUSE HOLDER FINGER SAFE COVER MOUNTING HOLES TAPPED 6 32 2 PLACES MOUNTING A 6 SLOTS 3 64 92 5 3 10 78 5 22 5 6 4 30 109 2 15 54 6 25 6 4 18 4 6 64 16 3 1 75 44 5 1 75 44 5 75 19 1 1 50 38 1 3 00 76 2 Electrical Connections Important Application Note To avoid erratic operation do not bundle the AC line and motor wires with signal or control wiring Also do not bundle motor wires ...

Страница 9: ...r equipment to which it is or will be connected Electrical shock can cause serious or fatal injury Only qualified personnel should attempt the installation and start up procedures The control can be turned on and off using the AC line disconnect Auto Inhibit circuitry automatically resets critical components each time the AC line is interrupted This along with Acceleration Start and CL provides a ...

Страница 10: ... 200 F F BC142 6 208 230 0 90 100 F L1 Step down operation PLUG IN HORSEPOWER RESISTOR ARMATURE FUSE KIT The Plug In Horsepower Resistor and Armature Fuse are supplied as a prepackaged kit Choose the appropriate Plug In Horsepower Resistor and Armature Fuse based on motor horsepower and voltage see Table 2 4 The Plug In Horsepower Resistor supplied separately must be installed to match the control...

Страница 11: ...r to control motor speed Connect the low side of the potentiometer to Terminal P1 Connect the wiper of the potentiometer to Terminal P2 Connect the high side of the potentiometer to Terminal P3 Figure 2 3 Remote Main Speed Potentiometer Connection Front View Main Speed Potentiometer EN C ONN1 P3 MAX P1 P2 High Wiper Low Terminal P3 Terminal P1 Terminal P2 Voltage Following Connection An isolated 0...

Страница 12: ...ch or contact is closed the motor will accelerate to the Main Speed Potentiometer setting When the switch or contact is opened the motor will decelerate to Stop An open collector PNP can be used in lieu of a switch or contact Figure 2 5 Enable Switch Or Contact Wired To The Enable Connector On to Run Open Collector C ONN1 MAX EN Open to Stop Close to Run or Contact Enable Switch the Mating Connect...

Страница 13: ...erminal P3 Terminal P2 P3 P1 P2 EN P3 P1 P2 Inhibit Circuit Connection The control can be stopped and started with an Inhibit Circuit close to stop Wire the switch or contact to Terminals I1 and I2 When the switch or contact is closed the motor will coast to stop When the switch or contact is opened the motor will accelerate to the Main Speed Potentiometer setting An open collector NPN can be conn...

Страница 14: ...sed with an 1800 RPM motor For a tachometer other than 7 Volts or 50 Volts per 1000 RPM or for a motor other than 1800 RPM an external 1 2 Watt resistor RT must be installed Install RT in series with the tachometer Connect one end of RT to Terminal T connect the other end of RT to the tachometer positive lead and connect the negative lead of the tachometer to Terminal I2 The value of RT Ω can be c...

Страница 15: ...e motor begins to accelerate according to the setting of the ACCEL Trimpot to the Main Speed Potentiometer setting Startup Adjustments The control has selectable jumpers which must be set before it can be used J1 AC Line Input Voltage Selection Catalog No BC142 5 and BC142 6 only Jumper J1 is factory set to the 230 position for 208 230 Volt AC line input For 115 Volt AC line input set Jumper J1 to...

Страница 16: ... are made with the main power applied an insulated adjustment tool must be used to prevent shock hazard and safety glasses must be worn TRIMPOT ADJUSTMENTS The control contains trimpots which have been factory set for most applications Some applications may require readjustment of the trimpots in order to tailor the control for a specific requirement Acceleration Trimpot ACCEL The ACCEL Trimpot is...

Страница 17: ... only an AC ammeter is available wire it in series with either AC line input lead 2 Set the Main Speed Potentiometer to approximately 30 50 clockwise position 3 Set the CL Trimpot fully counterclockwise 4 Load the motor shaft in accordance with application requirements 5 Apply power and the CL LED will illuminate red Rotate the CL Trimpot clockwise until the desired current reading is observed on ...

Страница 18: ...auses and the suggested corrective action for controls without optional forward brake reverse switch installed Table 2 4 Troubleshooting Guide without Optional Forward Brake Reverse Switch Symptom Possible Cause Suggested Corrective Action Motor is not running and Pilot Light not illuminated On Off AC Line Switch in Off Position Set On Off Switch to On Position Blown Line fuse Replace Line Fuse De...

Страница 19: ...e voltage and the correct setting of the Voltage Select Switch Defective motor worn brushes etc Repair or replace motor Optional Accessories 1 Auxiliary Heat Sink Catalog No BC143 Doubles the horsepower rating of the control 2 Barrier Terminal Board Catalog No BC147 Converts the quick connect terminals of the control to a barrier terminal block Contains PC board mounted line and armature fuse hold...

Страница 20: ...y P O Box 2400 Fort Smith AR 72902 2400 U S A Ph 1 479 646 4711 Fax 1 479 648 5792 International Fax 1 479 648 5895 www baldor com Baldor Electric Company MN704 All Rights Reserved Printed in USA A40249 Rev E 5 17 MN704 0517 ...

Отзывы: