MOD BUS TC P MA PPING
BAS IC FEATUR ES OF AWIN GW 100 G ATEWAY
18
3BNP1029 12 C
–
Access to configuration options
For access to configuration options, use the following log-in:
Username
= admin
Password
= admin
–
Access to monitoring screens
For access to monitoring screens only, use the following log-in:
Username
= monitor
Password
= monitor
The user must change password after first login or at least before commission-
ing the gateway.
3.5
Modbus TCP Mapping
The AWIN GW100 gateway can function as a protocol converter by mapping the HART com-
mand data from the WirelessHART network to Modbus TCP registers. This allows for easy in-
tegration of HART data into Modbus TCP host system.
3.6
Network Topology View
The AWIN GW100 gateway’s web interface provides a table with connectivity information of
WirelessHART devices. It also shows the strength of wireless mesh network in a color-coded
format.
3.7
Ethernet Network Connectivity
AWIN GW100’s Ethernet port shall be connected to an Ethernet switch. The switch can be
part of a host network. A typical host system on the host network could be a PLC or Automa-
tion controller using ModbusTCP protocol to communicate to the gateway.
The ethernet switch port connected to the AWIN GW100 gateway shall have Flow
Rate limiter enabled. Overall bandwidth should be capped to 10Mbps (recom-
mended). Avoid mixing field network with other networks, such as control and cli-
ent/server network. AWIN GW100 belongs to a field network only.
3.8
Hard Reset
A hardware reset restores the default IP address of
172.16.16.1
(subnet:
255.255.252.0
) and re-
sets the AWIN GW100 to factory default settings.
Содержание AWIN GW100
Страница 1: ... ENERGY INDUSTRIES ABB Wireless Industrial Network AWIN GW100 User Manual ...
Страница 2: ......
Страница 3: ... ENERGY INDUSTRIES AWIN GW100 ABB Wireless Industrial Network User Manual AWIN GW100 User Manual ...
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 68: ... Visit us www abb com oilandgas Document Number 3BNP102912 Rev C ...