3 Electrical Installation
20
User Guide OI/FET2XX–EN Rev. E
3.3 Input / Output Connections
3.3.1 Frequency Outputs
Caution.
Refer to the associated Data Sheets for input / output ratings.
Inductive loads must be suppressed or clamped to limit voltage swings.
Operation of outputs is programmable – see Programming Guide (COI/FET2XX–EN) for details.
External isolators are not normally required as the pulse and alarm circuit is electrically-separated
from all other AquaMaster 3 connections.
Capacitive loads must be inrush current limited.
Fully-floating pulse outputs may be subject to static damage, for example connecting to a floating
datalogger, unless 'COM' is operated within its galvanic isolation range (±35 V) from earth.
Fig. 3.6 Frequency Output Connections
Note.
Outputs 1 and 2 are not polarity-sensitive. The common connection for these outputs is
designated ‘COM’.
1 2 3 4 5 6
1 2 3 4 5 6
Telemetry, Electronic
Counters etc.
Counter / Totalizers
*Optional link for grounding floating
output – see Caution above.
PLC or Datalogger
Common
Input 1
Input 2
COM
O/P1
O/P2
OV*
COM
O/P1
O/P2
and / or
Forward Flow
Reverse Flow