24
EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 07/15
Installing Position Switch Actuator (Breaker)
Note: Later models of breakers (Q3 2015) are shipped with position switch bracket pre-installed.
Position switch actuator bracket can be installed on all versions of Retrofill EntelliGuard ACB for AKD6 LVS
(
). The steps of installation are as follows:`
Retrofills use the legacy position switch already mounted in the cubicle. If a new position switch has to be
installed, refer to the legacy position switch installation manual.
1.
Unpack the position switch bracket. Each bracket is provided with a pair of M6x16mm Allen-type bolts
and washers.
2.
Place the bracket on the bottom right side of the AKD6 base. Two locating holes are provided for mounting
of the position switch bracket.
3.
Fasten the two bolts to the locating holes after placing the washers to securely mount the bracket.
4.
The bracket is ready for use.
Figure 10. AKD-6—Position Switch Actuator (Breaker Side) and Parts
Level
Item or Part
Number
Description
Quantity
1
10105289P1
Position
Switch Brkt,
AKD-6
1
1
10100950P4
Washer M6
2
1
10100380P1
Serrated
Belleville
Washer M6
2
1
10100545P1
Cap Head
Screw M6x16
2
Note:
Individual hardware for the position switch actuator cannot be ordered separately. The item numbers
given are for reference only. The assembly comes as a unit or a kit.