Chapter 4 – Programming the AC 80
4-6
AC 80 User’s Manual
Essential Settings for
ACS 600 Standard Drive
Note that only the user-adjustable settings are represented here.
DRIDS
DRISTD
Base part:
Defining the value of POSITION:
Reference part:
NAME
Max. 20 characters, e.g. dataset_StdDrive
ACT
1
DS_NO
Dataset number (1 or 3)
WR_ENA
1 (Must be forced by a connection from the PC section)
NAME
Max. 20 characters, e.g. STD_DR_OP_MODULEBUS
POSITION
100 + address of the drive. See below.
IMPL
1
TYPE
ACS 600 STD
Position on
Optical
ModuleBus
Setting of drive
parameter 70.01
DRISTD POSITION setting
(100 × C Position)
1
17
101
2
18
102
3
19
103
• • •
• • •
• • •
12
28
112
REF1
Max. 20 characters, e.g. dataset_Standard_DR
REF2
Max. 20 characters