Advant
®
Controller 450 User’s Guide
Section 5.5.9 List of General Fault Finding Procedures and Hints
3BSE 002 415R701 Rev A
5-49
5.5.9.6 Check of Backup Power Supply
The backup power supply and battery diagnostics are indicated in the system status display (see
Section 5.5.2.1, System Status and Plain Language System Messages
) and by LEDs on the
Backup Power Supply SB510/511 front.
Fault finding in the controller cabinet is carried out as described in
The instructions are supported by the power supply block diagrams
in
.
5.5.9.7 Check of Processor Module
A description of the indicators on the module front is given to guide in the fault finding.
•
Red LED F means module fault or a software error (not so likely). Replace the processor
module.
•
Green LED RUN means module running normally.
The LED is turned off as a result of all kinds of system halts. If the green LED is turned off
read the system halt code on the character display and analyses the problem primarily as
described in
. Take recommended measures. If not successful
you should methodically follow the fault finding instructions elsewhere in this chapter.
Figure 5-20. Check of Backup Power Supply
SB510/511 L
Diagnostic
F
BP
BF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
Normal operation
Lost supply voltage or
Battery fault
------
1. See notes below
1), 2)
Replace battery unit SB522
Replacement or other measures
3)
ON
OFF
---
SB510/511 fault
Replace SB510/511
IP
ON
OFF
ON
ON
ON
ON
ON
---
Battery fault or SB510/511 fault
Replace battery unit first. Make a test. If not
successful replace SB510/511
Description of LED Indications
F
Fault
BF
Battery Fault
BP
Battery Powered
IP
Input Power
FC
Forced Charging
Check for lost supply voltage
1)
If SB510, check mains C or
tripped miniature circuit breaker in
power switch unit
2)
If SB511, check tripped miniature
blown fuse F1
2. Replace fuse in SB510/511
OFF
ON
OFF
ON
Battery fault
Replace battery unit SB522
Replacement instructions in
Replacement of Backup Power Supply
and
Section 5.5.10.7, Battery Exchange
3
)
circuit breaker in the 24 V distribution unit
Содержание Advant Controller 450
Страница 1: ...Advant OCS with Master software GYDQW RQWUROOHU User s Guide 3BSE 002 415R701 Rev A ...
Страница 26: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xvi ...
Страница 30: ...Advant Controller 450 User s Guide Table of Contents 3BSE 002 415R701 Rev A xx ...
Страница 488: ... GYDQW RQWUROOHU 8VHU V XLGH SSHQGL DUGZDUH 0RGXOHV A 48 3BSE 002 415R701 Rev A ...
Страница 496: ...Advant Controller 450 User s Guide Appendix C Delivery Documentation C 2 3BSE 002 415R701 Rev A ...
Страница 508: ...Advant Controller 450 User s Guide Appendix D Item Designations D 12 3BSE 002 415R701 Rev A ...
Страница 514: ...Advant Controller 450 User s Guide Appendix E Current Consumption and Heat Dissipation E 6 3BSE 002 415R701 Rev A ...
Страница 518: ...Advant Controller 450 User s Guide Appendix F Load Calculation F 4 3BSE 002 415R701 Rev A ...
Страница 522: ...Advant Controller 450 User s Guide Appendix G Memory Calculation G 4 3BSE 002 415R701 Rev A ...
Страница 528: ...Advant Controller 450 User s Guide Appendix H Halt Codes H 6 3BSE 002 415R701 Rev A ...
Страница 561: ...Advant Controller 450 User s Guide Index 3BSE 002 415R701 Rev A iii V Valve control 1 102 VT100 terminal 1 105 ...
Страница 562: ...Advant Controller 450 User s Guide Index iv 3BSE 002 415R701 Rev A ...
Страница 563: ......
Страница 564: ...3BSE 002 415R701 Rev A March 2000 ...