Guide on Installation and Debugging of Filters 15
Maximum, heat dissipation and noise level
Note!
The power of the selected filter shall be matched with that of the
frequency converter as far as possible, to obtain the best filtering effect.
If not matched, the filter with the higher power can be used for that with the
lower power, but the filtering effect may be reduced.
Harmonic filter
model
I
max
(A)
P
max
(kW)
I
filter
(A)
Noise
level
(
dB
)
Heat
dissipating
capacity
(W)
CFMm3/h
(
CFM
)
PIHF-0004-4-10
4.1
1.5
1.8
70
90
-
PIHF-0007-4-10
7.2
3
3
70
90
-
PIHF-0012-4-10
12.6
5.5
4.5
70
140
-
PIHF-0015-4-10
17
7.5
6
70
150
-
PIHF-0030-4-10
32
15
12
70
220
-
PIHF-0045-4-10
46
22
20
72
330
-
PIHF-0075-4-10
72
37
28
72
460
-
PIHF-0090-4-10
88
45
36
72
510
-
PIHF-0160-4-10
169
75
60
75
660
343(203)
PIHF-0205-4-10
206
110
75
75
850
343(203)
PIHF-0290-4-10
293
160
95
75
1050
592 (350)
PIHF-0363-4-10
363
200
125
75
1070
592 (350)
PIHF-0430-4-10
430
250
125
75
1150
592 (350)
PIHF-0505-4-10
505
250
-
80
1880
2*592 (2*350)
PIHF-0585-4-10
585
315
-
80
2100
2*592 (2*350)
PIHF-0650-4-10
650
355
-
80
2120
2*592 (2*350)
PIHF-0725-4-10
725
400
-
80
2200
2*1318
(2*780)
Rating
I
max
Maximum sustained current
P
max
Maximum power
I
filter
Filter branch current
Содержание ACx580-01 Series
Страница 4: ...4 Table of Contents ...
Страница 8: ...8 Guide on Installation and Debugging of Filters Wiring diagram of single filter 1 5 250kW ...
Страница 18: ...18 Guide on Installation and Debugging of Filters Product outline drawing S1 to S4 ...
Страница 19: ...Guide on Installation and Debugging of Filters 19 Product outline drawing S5 S6 ...