Parameters and firmware blocks
199
46.09
STALL FUNCTION
(see above)
Selects how the drive reacts to a motor stall condition. A stall condition is defined as follows:
• The drive is at stall current limit (
), and
• the output frequency is below the level set by parameter
• the conditions above have been valid longer than the time set by parameter
46.10
STALL CURR LIM
(see above)
Stall current limit in percent of the nominal current of the motor. See parameter
0 …1600%
Stall current limit.
46.11
STALL FREQ HI
(see above)
Stall frequency limit. See parameter
Note:
Setting the limit below 10 Hz is not recommended.
0.5…1000 Hz
Stall frequency limit.
46.12
STALL TIME
(see above)
Stall time. See parameter
.
0…3600 s
Stall time.
46.13
FAN CTRL MODE
FW block: None
Selects the fan control mode. Available in frame sizes A to D. See section
(0)
Normal
Control mode based on the modulator ON/OFF status.
(1)
Force OFF
Fan is always OFF.
(2)
Force ON
Fan is always ON.
(3)
Advanced
Control mode based on measured temperatures of the power stage,
braking chopper and interface board.
46.14
FAULT STOP MODE
FW block: None
Fault class selection for non-critical HW faults.
Use this parameter for configuring the following faults to the stop mode:
…
,
,
,
,
Bit
Function
0
Ena sup (Enable supervision)
0 = Disabled: Supervision disabled.
1 = Enabled: Supervision enabled.
1
Ena warn (Enable warning)
0 = Disabled
1 = Enabled: Drive generates an alarm upon a stall condition.
2
Ena fault (Enable fault)
0 = Disabled
1 = Enabled: Drive trips on a fault upon a stall condition.
Содержание ACSM1 Series
Страница 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Страница 4: ......
Страница 34: ...Drive programming using PC tools 34 ...
Страница 86: ...Drive control and features 86 ...
Страница 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Страница 302: ...Parameter data 302 ...
Страница 422: ...Application program template 422 ...
Страница 430: ...Appendix A Fieldbus control 430 ...
Страница 500: ...Appendix D Application examples 500 ...
Страница 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Страница 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...