Parameters 401
Module 2 emulated
Z-pulse offset
With interface module 2, defines when zero pulses are
emulated in relation to zero position received from the
encoder.
For example, with a value of 0.50000, a zero pulse is
emulated whenever the encoder position passes 0.5
revolutions. With a value of 0.00000, a zero pulse is emulated
whenever the encoder position passes zero position.
0
0.00000 … 1.00000
rev
Position of emulated zero pulses.
32767 =
1 rev
92
Settings for encoder 1.
Notes:
• The contents of the parameter group vary according to the
selected encoder type.
• It is recommended that encoder connection 1 (this group) is
used whenever possible since the data received through
that interface is fresher than the data received through
connection 2 (group
Selects the type of encoder/resolver 1.
None configured
None.
0
TTL
TTL. Module type (input): FEN-01 (X31), FEN-11 (X41) or
FEN-21 (X51).
1
TTL+
TTL+. Module type (input): FEN-01 (X32).
2
Absolute encoder
Absolute encoder. Module type (input): FEN-11 (X42).
3
Resolver
Resolver. Module type (input): FEN-21 (X52).
4
HTL
HTL. Module type (input): FEN-31 (X82).
5
HTL 1
HTL. Module type (input): FSE-31 (X31).
6
HTL 2
HTL. Module type (input): FSE-31 (X32). Not supported at the
time of publication.
7
Selects the interface module that the encoder is connected to.
(The physical locations and types of encoder interface
modules are defined in parameter group
.)
Module 1
Interface module 1.
0
Module 2
Interface module 2.
1
(Visible when a TTL, TTL+ or HTL encoder is selected)
Defines the pulse number per revolution.
2048
0…65535
Number of pulses.
-
(Visible when an absolute encoder is selected)
Defines the number of sine/cosine wave cycles within one
revolution.
Note:
This parameter need not be set when an EnDat or SSI
encoder is used in continuous mode. See parameter
0
0…65535
Number of sine/cosine wave cycles within one revolution.
-
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...