Parameters 167
Defines the real maximum value of the signal (selected by
parameter
) that corresponds to the
maximum required AO2 output value (defined by parameter
100.0
-32768.0 …
32767.0
Real signal value corresponding to maximum AO2 output
value.
1 = 1
Defines the minimum output value for analog output AO2.
See also drawing at parameter
0.000 mA
0.000 … 22.000 mA Minimum AO2 output value.
1000 = 1 mA
Defines the maximum output value for analog output AO2.
See also drawing at parameter
20.000 mA
0.000 … 22.000 mA Maximum AO2 output value.
1000 = 1 mA
Storage parameter for controlling analog output AO1 eg.
through fieldbus.
In
, select
. Then set this
parameter as the target of the incoming value data.
With the embedded fieldbus interface, simply set the target
selection parameter of that particular data (
)
to
0.00
-327.68 … 327.67
Storage parameter for AO1.
100 = 1
Storage parameter for controlling analog output AO2 eg.
through fieldbus.
In
, select
. Then set this
parameter as the target of the incoming value data.
With the embedded fieldbus interface, simply set the target
selection parameter of that particular data (
)
to
0.00
-327.68 … 327.67
Storage parameter for AO2.
100 = 1
14
Configuration of I/O extension module 1.
See also section
(page
Note:
The contents of the parameter group vary according to
the selected I/O extension module type.
Activates (and specifies the type of) I/O extension module 1.
Note:
This parameter cannot be changed while the drive is
running.
None
Inactive.
0
FIO-01
FIO-01.
1
FIO-11
FIO-11.
2
FDIO-01
FDIO-01.
3
FAIO-01
FAIO-01.
4
Specifies the slot (1…3) on the control unit of the drive into
which the I/O extension module is installed. Alternatively,
specifies the node ID of the slot on an FEA-03 extension
adapter.
Note:
This parameter cannot be changed while the drive is
running.
Slot 1
Slot 1.
1
Slot 2
Slot 2.
2
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...