Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Not selected / uint32
When parameter
is set to
or
, this parameter selects the
source of actual value 2 transmitted to the fieldbus
network through fieldbus adapter A.
FBA A act2
transparent source
50.11
0
No source selected.
Not selected
See
Terms and abbreviations (page 169)
Other [value]
Disable / uint16
Enables the display of raw (unmodified) data received
from and sent to fieldbus adapter A in parameters
…
This functionality should only be used for debugging.
Note: This parameter cannot be changed while the
drive is running.
FBA A debug mode
50.12
0
Display of raw data from fieldbus adapter A disabled.
Disable
1
Display of raw data from fieldbus adapter A enabled.
Fast
0 / uint32
Displays the raw (unmodified) control word sent by the
master (PLC) to fieldbus adapter A if debugging is
enabled by parameter
This parameter is read-only.
FBA A control word
50.13
1 = 1
Control word sent by master to fieldbus adapter A.
00000000…FFFFFFFFh
- / int32
Displays raw (unmodified) reference REF1 sent by the
master (PLC) to fieldbus adapter A if debugging is
enabled by parameter
This parameter is read-only.
FBA A reference 1
50.14
- / int32
Displays raw (unmodified) reference REF2 sent by the
master (PLC) to fieldbus adapter A if debugging is
enabled by parameter
This parameter is read-only.
FBA A reference 2
50.15
0 / uint32
Displays the raw (unmodified) status word sent by
fieldbus adapter A to the master (PLC) if debugging is
enabled by parameter
This parameter is read-only.
FBA A status word
50.16
1 = 1
Status word sent by fieldbus adapter A to master.
00000000…FFFFFFFFh
- / int32
Displays raw (unmodified) actual value ACT1 sent by
fieldbus adapter A to the master (PLC) if debugging is
enabled by parameter
This parameter is read-only.
FBA A actual value 1
50.17
- / int32
Displays raw (unmodified) actual value ACT2 sent by
fieldbus adapter A to the master (PLC) if debugging is
enabled by parameter
This parameter is read-only.
FBA A actual value 2
50.18
466 Parameters
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...