Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
1 = 1 s / 1 = 1 s
Motor thermal time constant.
100...10000 s
No action / uint16
Selects the action taken when motor overload is
detected.
See section
Motor overload protection (page 132)
Motor overload
action
35.56
0
No action taken.
No action
1
Drive generates warning
when
the motor is overloaded to the warning level, that is,
parameter
reaches value
88.0%.
Warning only
2
Drive generates warning
when
the motor is overloaded to the warning level, that is,
parameter
reaches value
88.0%.
Drive trips on fault
when the motor
is overloaded to the fault level, that is, parameter
reaches value 100.0%.
Warning and fault
Class 20 / uint16
Defines the motor overload class to be used. The class
of protection is specified by the user as the time for
tripping at 7.2 times (IEC 60947-4-1) or 6 times (NEMA
ICS) the tripping level current.
See section
Motor overload protection (page 132)
Motor overload class
35.57
0
Motor overload class 5.
Class 5
1
Motor overload class 10.
Class 10
2
Motor overload class 20.
Class 20
3
Motor overload class 30.
Class 30
4
Motor overload class 40.
Class 40
0.0 % / real32
Shows the calculated temperature of the motor cable.
See section
.
102% = overtemperature warning (
)
106% = overtemperature fault (
)
This parameter is read-only.
Cable temperature
35.60
1 = 1 % / 10 = 1 %
Calculated temperature of motor cable.
0.0 ... 200.0 %
10000.00 A / real32
Specifies the continuous current of the motor cable
for the thermal protection function in the control
program.
WARNING!
The value entered in this parameter must be
limited according to all factors affecting the
loadability of the cable, such as ambient
temperature, cabling arrangement, and
shrouding. Refer to the technical data from the
cable manufacturer.
Cable nominal
current
35.61
1 = 1 A / 100 = 1 A
Continuous current-carrying capacity of motor cable.
0.00 ... 10000.00 A
408 Parameters
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...