Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
1 = 1
0000h…FFFFh
0.00 A / real32
Sets a custom motor current fault limit.
The drive automatically sets an internal motor current
limit according to the drive hardware. The internal limit
is appropriate in most cases, but this parameter can
be used to set a lower current limit, for example, to
protect a permanent magnet motor from
demagnetization.
Note: The limit defines the maximum peak current of
one phase.
With this parameter at 0.0 A, only the internal limit is
in force.
Overcurrent fault
limit
31.42
- / -
Custom motor current fault limit. For scaling, see
parameter
0.00 ... 30000.00 A
Coast / uint16
Selects the stop mode when a non-critical fault occurs.
Fault action
31.54
0
The drive coasts to a stop.
Coast
1
The drive follows the ramp specified for an emergency
stop in parameter
.
Emergency ramp
Fault / uint16
Selects how the drive reacts when the communication
to an I/O extension module fails.
Ext I/O comm loss
event
31.55
0
No action taken.
No action
1
The drive generates a warning,
.
Warning
2
The drive trips on a fault,
Fault
- / uint16
Shows the status bits for sync loss supervision activity.
Sync loss status
word
31.200
1 = Sync loss condition is detected.
Triggered
b0
1 = Sync loss condition is detected and
warning is triggered.
Triggered as
warning
b1
1 = Sync loss condition is detected and
fault is triggered.
Triggered as fault
b2
1 = Supervision function is enabled and condition of
cos phi signal is monitored.
Function enabled
b3
1 = Drive output value is above the value defined in
parameter
31.202 Sync loss minimum detection limit
Frequency above
detection limit
b4
1 = Actual cos phi value is below the value defined in
parameter
31.206 Sync loss cos phi minimum level
Cos phi below
minimum
b5
1 = Cos phi value has dropped more than or is equal to
the limit defined by parameter
Cos phi drop
detected
b6
Reserved
b7…15
1 = 1
0000h…FFFFh
Parameters 377
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...