Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
5 s / real32
Defines the period between previous sample and actual
sample of cos phi values used to detect the sync loss
condition.
The below block diagram shows the control logic for a
sample memory area of 10 samples.
If the sample period is set as
•
1 second, the first sample is compared after 1
second, and the next samples are compared after
100 ms.
•
10 seconds, the first sample is compared after 10
seconds, and the next samples are compared after
1 second.
•
120 seconds, the first sample is compared after
120 seconds, and the next samples are compared
after 12 seconds.
Sync loss sample
period
31.203
1 = 1 s / 1 = 1 s
Sync loss sample period.
0...120 s
0.5 s / real32
Defines the filter time for signal
1.25 INU momentary
cos φ used for sync loss supervision function.
Sync loss cos phi
filter time
31.204
10 = 1 s / 1 = 1 s
Filter time.
0.0 ... 120.0 s
50.0% / real32
Defines the cos phi drop limit for the Sync loss
supervision function.
If the drop from previous to actual cos phi samples is
equal to or larger than the limit, the Sync loss condition
occurs. Note that the function detects a sync loss
condition only if the drive output frequency is above
the minimum detection limit (
The motor is not in synchronization condition, when:
Previous cos phi sample - Actual cos phi sample ≤
Previous cos phi sample * p.31.205/100
Sync loss cos phi
drop
31.205
10 = 1% / 1 = 1%
Synchronization loss cos phi drop in percent.
0.0 ... 100.0%
0.30 / real32
Defines the minimum level of actual cos phi below
which motor is out of synchronization.
Sync loss cos phi
minimum level
31.206
100 = 1 / 1 = 1
Synchronization loss cos phi minimum level.
0.00 ... 1.00
Parameters 379
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...