Implementing the Safe torque off function
See the hardware manual for implementing the Safe torque off function.
Implementing the Prevention of unexpected start-up
function
■
ACS880 cabinets
You can order the drive with a Prevention of unexpected start-up (POUS) function. The
POUS function enables short-time maintenance work (like cleaning) on the non-electrical
parts of the machinery without switching off and disconnecting the drive.
See the appropriate manual for more information.
Manual code (Eng-
lish)
User’s manual
Option
code
Prevention of unexpected start-up, with FSO-xx safety functions module
+Q950
Prevention of unexpected start-up, with safety relay
+Q957
■
Modules
POUS is not available as an option from ABB.
Implementing the functions provided by the FSO-xx safety
functions module
■
ACS880 single drive cabinets
You can order the drive with an FSO-12 or FSO-21 safety functions module (Q972
or +Q973) which enables the implementation of functions such as Safe brake control (SBC),
Safe stop 1 (SS1), Safe stop emergency (SSE), Safely limited speed (SLS) and Safe
maximum speed (SMS).
The settings of the FSO-xx module are at default when delivered from the factory. The wiring
of the external safety circuit and configuration of the FSO-xx module are the responsibility
of the user.
The FSO-xx module reserves the standard Safe torque off (STO) connection of the inverter
control unit. STO can still be utilized by other safety circuits through the FSO-xx.
See the appropriate manual for more information.
Code
Name
3AXD50000015612
FSO-12 safety functions module user's manual
3AXD50000015614
FSO-21 safety functions module user's manual
■
Modules
You can order a safety function module from ABB. The cabinet builder can use the module
for implementing various safety functions.