26 Start-up and acceptance test
Start-up and acceptance test
You need the Drive composer pro PC tool to perform the start-up and acceptance test.
Initial status: Make sure that the drive is ready for use, that is, you have done the tasks of
the drive start-up procedure. See the hardware manual.
Action
WARNING!
Obey the
, page
. If you ignore them, injury or death, or
damage to the equipment can occur.
Checks and settings with no voltage connected
After you have done the wiring to the POUS switch and indication lamp, check the connections
against the appropriate circuit diagrams. Make sure that the POUS request is not on (the POUS
switch is closed).
Drives with R8i inverter modules: Check that the STO OUT output on the inverter control unit [A41] is
chained to the STO inputs of all inverter modules. The STO circuit is disabled in spare part modules.
Settings with voltage connected
Make sure that the parameters relevant to the safety function are set as defined in chapter
and according to your application.
Create a backup file of the drive (button
Backup/restore
in the Drive composer pro PC tool).
Save the FSO safety file (button
Save safety file
in the Drive composer pro PC tool).
Note
: The FSO safety file is not included in the drive backup process.
Acceptance test procedure
Make sure that you can run and stop the motors freely during the test.
We recommend that you monitor these signals with the Drive composer pro PC tool:
• 01.01 Motor speed used
(rpm)
• 01.02 Motor speed estimated
(rpm)
•
01.07 Motor current
(A)
• 01.10 Motor torque
(%)
• 23.01 Speed ref ramp input
(rpm)
• 23.02 Speed ref ramp output
(rpm)
• 90.01 Motor speed for control
(rpm)
• 90.10 Encoder 1 speed
(rpm)
• 200.01 FSO speed ch1
(rpm)
• 200.02 FSO speed ch2
(rpm)
• 200.03 FSO DI status
• 200.04 FSO DO status
• 200.05 FSO control word 1
• 200.06 FSO control word 2
• 200.07 FSO status word 1
• 200.08 FSO status word 2
• 200.09 Drive status word 1
• 200.10 Drive status word 2
Close the disconnector and switch on the power. Do not start the motors yet (you should activate the
POUS function only when the motors are stopped).
Activate the POUS function by switching off the POUS switch.