What to do
Cause
Event name /
Aux. code
Code
(hex)
because of limited switching
frequency (eg. by parameter
).
below
requested
Replace control unit battery.
The battery of the control unit is low.
Control unit
battery
A5F4
This warning can be suppressed using
parameter
.
Avoid forcing unnecessary parameter
saves by parameter
or cyclic
The flash memory (in the memory unit)
has been erased too frequently,
Flash erase
speed
exceeded
A682
parameter writes (such as user logger
triggering through parameters).
compromising the lifetime of the
memory.
Check the auxiliary code (format XYYY
YZZZ). “X” specifies the source of
warning (1: generic flash erase
supervision). “ZZZ” specifies the flash
subsector number that generated the
warning.
Check the auxiliary code. See actions
for each code below.
An error in saving data to the power
unit.
Data saving
to power unit
A683
Cycle the power to the drive. If the
control unit is externally powered,
An error is preventing saving from
initializing.
0, 1
also reboot the control unit (using
parameter
or by cycling its power. If the
problem persists, contact your local
ABB representative.
Cycle the power to the drive. If the
control unit is externally powered,
Write error.
2
also reboot the control unit (using
parameter
or by cycling its power. If the
problem persists, contact your local
ABB representative.
Check the auxiliary code. See actions
for each code below.
Error related to SD card used to store
data (BCU control unit only).
SD card
A684
Insert a compatible, writable SD
card into the SD CARD slot of the
BCU control unit.
No SD card.
0
Insert a compatible, writable SD
card into the SD CARD slot of the
BCU control unit.
SD card write-protected.
1
Insert a compatible, writable SD
card into the SD CARD slot of the
BCU control unit.
SD card unreadable.
2
Check the supply voltage.
Power fail saving is requested too
frequently. Because of the limited
Power fail
saving
A685
saving interval, some of the requests
do not trigger the saving and power
fail data may be lost. This may be
caused by DC voltage oscillation.
Check that all necessary approved
(reference) checksums (
…
The calculated parameter checksum
does not match any enabled reference
checksum.
Checksum
mismatch
A686
Fault tracing 575
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...