Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
50.00 Hz / real32
Defines the nominal motor frequency. This setting must
match the value on the rating plate of the motor.
Note: This parameter cannot be changed while the
drive is running.
Motor nominal
frequency
99.8
10 = 1 Hz / 100 = 1 Hz
Nominal frequency of the motor.
0.00 ... 1000.00 Hz
0 rpm / real32
Defines the nominal motor speed. The setting must
match the value on the rating plate of the motor.
Note: This parameter cannot be changed while the
drive is running.
Note: (Asynchronous generator) Nominal speed needs
to be adjusted as running the generator as a motor.
Motor nominal
speed
99.9
1 = 1 rpm / 1 = 1 rpm
Nominal speed of the motor.
0...30000 rpm
- / real32
Defines the nominal motor power. The setting must
match the value on the rating plate of the motor. If
nominal power is not shown on the rating plate,
nominal torque can be entered instead in parameter
If multiple motors are connected to the drive, enter the
total power of the motors.
The unit is selected by parameter
Note: This parameter cannot be changed while the
drive is running.
Motor nominal
power
99.10
1 = 1 kW or hp / 100 =
1 kW or hp
Nominal power of the motor.
0.00 ... 10000.00 kW
or hp
0.00 / real32
Defines the cosphi of the motor for a more accurate
motor model. The value is not obligatory, but is useful
with an asynchronous motor, especially when
performing a standstill identification run. With a
permanent magnet or synchronous reluctance motor,
this value is not needed.
Note: Do not enter an estimated value. If you do not
know the exact value, leave the parameter at zero.
Note: This parameter cannot be changed while the
drive is running.
Motor nominal cos
φ
99.11
100 = 1 / 100 = 1
Cosphi of the motor.
0.00 ... 1.00
0.000 Nm or lb·ft /
uint32
Defines the nominal motor shaft torque. This value can
be given instead of nominal power (
) if shown on
the rating plate of the motor.
The unit is selected by parameter
Note: This setting is an alternative to the nominal
power value (
). If both are entered,
takes
priority.
Note: This parameter cannot be changed while the
drive is running.
Motor nominal
torque
99.12
538 Parameters
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...