Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
12
Data is read from the followers with node addresses 3
and 4.
Follower nodes 3+4
14
Data is read from the followers with node addresses
2, 3 and 4.
Follower nodes
2+3+4
0
None.
None
FALSE / uint32
When parameter
is set to
or
, this parameter selects a source that
forces the drive to be the master on the
master/follower link.
1 = Drive is master on the master/follower link
Force master
60.15
0
0.
FALSE
1
1.
TRUE
See
Terms and abbreviations (page 130)
.
Other [bit]
FALSE / uint32
When parameter
is set to
or
, this parameter selects a source that
forces the drive to be a follower on the master/follower
link.
1 = Drive is follower on the master/follower link
Force follower
60.16
0
0.
FALSE
1
1.
TRUE
See
Terms and abbreviations (page 130)
.
Other [bit]
Fault / uint16
(Effective in the master only.) Selects how the drive
reacts to a fault in a follower.
See also parameter
60.23 M/F status supervision sel 1
.
Note: Each follower must be configured to transmit its
status word as one of the three data words in
parameters
…
. In the master, the
corresponding target parameter (
) must be
set to
.
Follower fault action
60.17
0
No action taken. Unaffected drives on the
master/follower link will continue running.
No action
1
The drive generates a warning (
).
Warning
2
Drive trips on
. All followers will be
stopped.
Fault
Always / uint16
Interlocks the starting of the master to the status of
the followers.
See also parameter
60.23 M/F status supervision sel 1
.
Note: Each follower must be configured to transmit its
status word as one of the three data words in
parameters
…
. In the master, the
corresponding target parameter (
) must be
set to
.
Follower enable
60.18
0
The master can only be started if all followers are ready
to switch on (bit 0 of
in each
follower is on).
MSW bit 0
Parameters 409
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...