Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Fast / uint16
Selects the standard I/O communication time level.
IO time level
selection
10.90
500
Standard I/O time level 500 us.
Fast
2000
Standard I/O time level 2 ms.
Normal
- / uint16
Storage parameter for controlling the relay outputs
and digital input/outputs eg. through the embedded
fieldbus interface.
To control the relay outputs (RO) and the digital
input/outputs (DIO) of the drive, send a control word
with the bit assignments shown below as Modbus I/O
data. Set the target selection parameter of that
particular data (
) to
. In the source selection parameter of the desired
output, select the appropriate bit of this word.
RO/DIO control
word
10.99
Source bit for relay output RO1. See parameter
.
RO1
b0
Source bit for relay output RO2. See parameter
RO2
b1
Source bit for relay output RO3. See parameter
.
RO3
b2
Reserved
b3…7
Source bit for digital input/output DIO1 (see parameter
.
DIO1
b8
Source bit for digital input/output DIO2 (see parameter
DIO2
b9
Reserved
b10…15
1 = 1
0000h…FFFFh
Parameters 179
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...