308 Parameters
Defines the measuring range for the Pump level control
function.
0.00 m, ft or
Joints
0.00...100000.00 m
Measuring range
10 = 1 m, ft or
Joints
Defines the gain for the Pump level control function.
Note
: This value should be kept low to avoid unwanted
oscillation from the drive speed reference causing the
pump to cycle up and down in rpm.
0.00
0.00...5.00
Proportional gain
100 = 1
Defines the integration time for the Pump level control
function.
Note
: This value should be kept at a fairly large value to
avoid unwanted oscillation from the drive speed reference
causing the pump to cycle up and down in rpm.
0.000 s
0.000...3600.000 s
Integration time
10 = 1 s
Selects the reaction characteristics of the Pump level
control function.
Disable
Disable
When the feedback signal selected by
is less than
, the PI regulator
output increases, causing the speed reference to increase.
0
Enable
When the feedback signal selected by
is greater than
, the PI
regulator output increases, causing the speed reference to
increase.
1
Source selection (see
on
page
-
Enables the Sleep and wake up function. See section
on page
.
Disable
Disable
Disables sleep and wake up control function.
0
Enable
Enables sleep and wake up control function.
1
Source selection (see
on
page
-
Enables the warning for the Sleep and wake up function.
See section
.
Disable
Disable
Disables sleep and wake up warning.
0
Enable
Enables sleep and wake up warning.
1
Source selection (see
on
page
-
Selects the sleep function type: sleep at low limit or sleep
at high limit.
Low limit
Low limit
If
is enabled and
is less than or equal to
and the condition is true longer than the time
, the pump will shut down.
The Sleep function is active until
increases to a level greater than or equal to
See section
.
0
No.
Name/Value
Description
Def/
FbEq16
Содержание ACS880 ESP
Страница 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Страница 4: ......
Страница 28: ...28 PCP ESP control start up ...
Страница 30: ...30 Using the control panel ...
Страница 94: ...94 Standard programposi features ...
Страница 100: ...100 Default control connections ...
Страница 360: ...360 Parameters ...
Страница 362: ...362 Additional parameter data Fieldbus addresses Refer to the User s Manual of the fieldbus adapter ...
Страница 436: ...436 Fault tracing ...
Страница 486: ...486 Control chain diagrams ...
Страница 492: ...492 Appendix ESP with step up transformer and sine filter ...
Страница 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...