Auxiliary circuit current consumption
Auxiliary circuit current consumption varies depending on the actual drive configuration and
options. Contact ABB for the delivery-specific value.
Energy efficiency data (EU ecodesign)
Energy efficiency data is not provided for the drive/unit. The multidrives are not in the scope
of the EU ecodesign requirements (Regulation EU/2019/1781) or the UK ecodesign
requirements (Regulation SI 2021 No. 745).
Protection classes
IP42 (standard), IP54 (B055)
Degrees of protection
(IEC/EN 60529)
UL Type 1 (standard), UL Type 12 (B055). For indoor use only.
Enclosure types (UL50)
III, except for auxiliary power connections (fan, control, heating, lighting, cooling
unit pump etc) which are category II.
Overvoltage category
(IEC/EN 60664-1)
I
Protective class
(IEC/EN 61800-5-1)
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Transportation
in the protective package
Storage
in the protective package
Operation
installed for stationary
use
-
-
0…2000 m (0…6562 ft)
above sea level. For alti-
tudes over 2000 m, contact
ABB.
Installation site altitude
Output derated above 1000
m (3281 ft).
-40 to +70 °C (-
40 to +158 °F)
-40 to +70 °C (-
40 to +158 °F)
0 … +45 °C
(+32 … +113 °F), no con-
densation allowed. Output
derated in the range
+45 … +55 °C
(+113 … +131 °F).
Air temperature
Max. 95%
Max. 95%
Max. 95%
Relative humidity
No condensation allowed. Maximum allowed relative humidity is 60% in the presence
of corrosive gases.
Technical data 59
Содержание ACS880-7407LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 7407LC semiconductor switch units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 22: ...22 ...
Страница 30: ...30 ...
Страница 34: ...34 ...
Страница 36: ...36 ...
Страница 54: ...54 ...
Страница 56: ...56 ...