Selecting the power cables
■
General guidelines
Select the input power and motor cables according to local regulations.
•
Current:
Select a cable capable of carrying the maximum load current and suitable for
the prospective short-circuit provided by the supply network. The method of installation
and ambient temperature affect the cable current carrying capacity. Obey local
regulations and laws.
•
Temperature:
For an IEC installation, select a cable rated for at least 70 °C (158 °F)
maximum permissible temperature of conductor in continuous use.
For North America, select a cable rated for at least 75 °C (167 °F).
Important: For certain product types or option configurations higher temperature rating
may be required. See the technical data for details.
•
Voltage:
600 V AC cable is accepted for up to 500 V AC. 750 V AC cable is accepted
for up to 600 V AC. 1000 V AC cable is accepted for up to 690 V AC.
To comply with the EMC requirements of the CE mark, use one of the preferred cable types.
See
Preferred power cable types (page 79)
Symmetrical shielded cable reduces electromagnetic emission of the whole drive system
as well as the stress on motor insulation, bearing currents and wear.
Metal conduit reduces electromagnetic emission of the whole drive system.
■
Typical power cable sizes
See the technical data.
■
Power cable types
Preferred power cable types
This section presents the preferred cable types. Make sure that the selected cable type also
complies with local/state/country electrical codes.
Use as motor cabling
Use as input power cabling
Cable type
Yes
Yes
PE
Symmetrical shielded (or armored)
cable with three phase conductors
and concentric PE conductor as
shield (or armor)
Yes
Yes
PE
Symmetrical shielded (or armored)
cable with three phase conductors
and symmetrically constructed PE
conductor and a shield (or armor)
Guidelines for planning the electrical installation 79
Содержание ACS880-37LC-0390A-7
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 37LC drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 13: ...16 Resistor braking Further information Table of contents 13 ...
Страница 14: ...14 ...
Страница 24: ...24 ...
Страница 28: ...28 ...
Страница 50: ...50 ...
Страница 70: ...70 Mechanical installation ...
Страница 110: ...10 110 Electrical installation ...
Страница 113: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 113 11 ...
Страница 134: ...134 ...
Страница 140: ...140 ...
Страница 148: ...a b c 148 Maintenance ...
Страница 151: ...4 5 6 Maintenance 151 ...
Страница 164: ...164 ...
Страница 174: ...174 ...
Страница 196: ...196 ...
Страница 199: ... Dimension drawing examples ACS880 37LC 0390A 7 with main contactor Dimensions 199 ...
Страница 201: ...ACS880 37LC 1270A 7 with common motor terminal cubicle Dimensions 201 ...
Страница 202: ...ACS880 37LC 1940A 7 with common motor terminal cubicle 202 Dimensions ...
Страница 205: ...Location and size of input terminals Contact ABB for details Dimensions 205 ...
Страница 206: ... 100 kA input cubicle option F274 206 Dimensions ...
Страница 208: ...Inverter module cubicle with two R8i modules bottom cable exit 208 Dimensions ...
Страница 209: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 209 ...
Страница 210: ...Brake chopper cubicle 210 Dimensions ...
Страница 211: ... Units with common motor terminal cubicle H359 Cubicle width 300 mm bottom cable exit Dimensions 211 ...
Страница 212: ...Cubicle width 300 mm top cable exit 212 Dimensions ...
Страница 213: ...Cubicle width 400 mm bottom cable exit Dimensions 213 ...
Страница 214: ...Cubicle width 400 mm top cable exit 214 Dimensions ...
Страница 215: ...Cubicle width 600 mm bottom cable exit Dimensions 215 ...
Страница 216: ...Cubicle width 600 mm top cable exit 216 Dimensions ...
Страница 238: ...238 ...
Страница 240: ...240 ...