![ABB ACS880-207 Скачать руководство пользователя страница 132](http://html.mh-extra.com/html/abb/acs880-207/acs880-207_hardware-manual_3316132.webp)
Electrical power network specification
400 V units: 380…415 V AC 3-phase ± 10%. This is indicated in the type designation
label as typical input voltage level (3~ 400 V AC).
Voltage (
U
1
)
500 V units: 380…500 V AC 3-phase ± 10%. This is indicated in the type designation
label as typical input voltage levels (3~ 400/480/500 V AC).
690 V units: 525…690 V AC 3-phase ± 10% (525…600 V AC ± 10% in UL/CSA
installations, or corner-grounded TN systems). This is indicated in the type desig-
nation label as typical input voltage levels (3~ 525/600/690 V AC).
TN (grounded) and IT (ungrounded) systems
Network type
50/60 Hz, variation ± 5% of nominal frequency
Frequency
Max. ± 3% of nominal phase-to-phase input voltage
Imbalance
Supply units with the ABB-defined main switch-disconnector and fuses:
Short-circuit withstand
strength (IEC/EN 61439-1)
•Rated peak withstand current
I
pk
= 105 kA
•Rated short-time withstand current
I
cw
= 50 kA/1 s
Supply units with ABB-defined main circuit breaker and fuses:
•Rated peak withstand current
I
pk
= 143 kA
•Rated short-time withstand current
I
cw
= 65 kA/1 s
The drive is suitable for use on a circuit capable of delivering not more than
100,000 rms symmetrical amperes at 600 V maximum when the input cable is
protected with class T fuses.
Short-circuit current protec-
tion (UL 508A, CSA C22.2
No. 14-13)
0.99
Fundamental power factor
(cos phi
1
)
Harmonics are below the limits defined in IEEE519.
Harmonic distortion
THD Current [%]
THD Voltage [%]
R
sc
2.5
1)
3
20
1)
0.8
100
I
n
n
th
harmonic component
I
N
nominal current
1) Other loads may influence the THD value.
THD = Total Harmonic Distortion (THD). The voltage THD depends on the short-
circuit ratio (
R
sc
). The spectrum of the distortion also contains interharmonics.
R
sc
=
I
sc
/
I
N
I
sc
= short-circuit current at point of common coupling (PCC)
I
N
= IGBT supply unit nominal current
Control unit connection data (BCU)
See chapter
132 Technical data
Содержание ACS880-207
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 207 IGBT supply units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 53: ... 3 3 Electrical installation 53 11 ...
Страница 54: ...3 54 Electrical installation ...
Страница 81: ...4 5 6 7 8 6 10 10 Maintenance 81 ...
Страница 94: ...5 6 10 3 4 7 9 8 94 Maintenance ...
Страница 99: ... Maintenance 99 ...
Страница 100: ... 100 Maintenance ...
Страница 103: ...5 6 3 4 8 9 7 Maintenance 103 ...
Страница 107: ...5 6 3 4 7 Maintenance 107 ...